Appendix 6 Instruction Manual for Compliance with UL/c-UL 
MITSUBISHI CNC
Appendix 6 - 6
(4) AC Reactor (D/DH-AL)
Input/Output (L11, L12, L13, L21, L22, L23)
The wire connected with AC Reactor becomes same size as TE1 of the selected Power supply unit.
(5) Notes of Round Crimping Terminals and Terminal Block
The non-insulation ring tongue must have the insulated sleeving described below to prevent electric 
shock.
The insulated sleeve must be provided with SUMITOMO ELECTRIC FINE POLYMER INC. (File No.: 
E48762, Catalogue No.: SUMITUBE F(Z) or 939) per the illustration below.
Appendix 6-2-6 Motor Over Load Protection 
Spindle drive unit MDS-D/DH-SP/SP2/SPJ3 and Servo drive unit MDS-D/DH/DM-V1/V2/V3/SVJ3 series 
have each solid-state motor over load protection. (The motor full load current is the same as rated current.)
When adjusting the level of motor over load, set the parameter as follows.
(1) MDS-D/DH-SP/SP2/SPJ3 (Spindle drive unit)
(2) MDS-D/DH/DM-V1/V2/V3/SVJ3 (Servo drive unit)
Appendix 6-2-7 Flange of servo motor
Mount the servo motor on a flange which has the following size or produces an equivalent or higher heat 
dissipation effect:
Type
D-AL-
7.5K, 11K
18.5K to 45K
55K
DH-AL-
7.5K, 11K
18.5K to 75K
---
Terminal 
Screw 
Size
L11, L12, L13, L21, L22, L23
M5
M6
M10
Torque [lb in/ N m]
17.7/2.0
35.4/4.0
97.3/11.0
Parameter No. 
Parameter abbr.
Parameter Name
Setting Procedure
Standard Setting Value
Setting Range
SP021
OLT*
Overload
time constant
Set the time constant for overload de-
tection. (Unit: 1 second.)
60s
0 to 15300s
SP022
OLL
Overload
detection level
Set the overload current detection level 
with a percentage (%) of the rating.
120%
1 to 200%
Parameter No. 
Parameter abbr.
Parameter Name
Setting Procedure
Standard Setting Value
Setting Range
SV021
OLT
Overload
time constant
Set the time constant for overload de-
tection. (Unit: 1 second.)
60s
1 to 300s
SV022
OLL
Overload
detection level
Set the overload current detection level 
with a percentage (%) of the stall rating.
150%
1 to 500%
Flange size
(mm)
Servo Motor
HF, HF-H, HP, HP-H, HF-KP, HF-MP, HF-SP
150x150x6
50 to 100W
250x250x6
200 to 400W
250x250x12
0.5 to 1.5kW
300x300x20
2.0 to 7.0kW
800x800x35
9.0 to 11.0kW
Insulated sleeve
Non-insulated terminal
Insulation 
distance
Non-insulated 
terminal