7. AUXILIARY FUNCTION 
 
7.17.4 Timing chart for alarm history read 
A method for reading alarm history stored in the alarm history area is shown below. 
ON
OFF
Page 1
Page 2
Page 3
sscGetAlarmHistoryData function
Alarm history read
command (ALHR)
Alarm history read
complete (ALHRF)
Alarm history read page
number
Host
controller
Position
board
ON
OFF
 
 
 
POINT 
 
The alarm history is stored in the alarm history area of the position board 
flash ROM in ring buffer format. The data is read from the oldest data first 
when transmitting to the dual port memory. 
 
API LIBRARY  
Use the sscGetAlarmHistoryData function to read the alarm history. Calculate 
the largest page number (divide the number of valid events by 4 and round up 
to nearest whole number) to be read by using the number of valid events got 
with the sscCheckAlarmHistoryEventNum function. 
Use this function to get alarm history data from page 1 to the largest page 
number to be read.