11. PARAMETERS 
 
11.1 System parameters 
POINT 
 
The settings for the parameters with a * mark at the front of the abbreviation 
are validated when the system is restarted. 
 
 
Parameter 
No. 
Symbol Name 
Initial 
Value
Units
Setting 
range 
Function 
0001 
*SYSOP1  System option 1 
0000h
 
0000h 
to 0002h
0
0
Set the control cycle
0: 0.88ms
1: 0.44ms
2: 0.22ms
SSCNET communication method
Set the SSCNET communication
method.
0: SSCNET    /H
(Note) SSCNET communication
           method is shared in lines
           1 and 2.
0002 
*SYSOP2  System option 2 
0000h
 
0000h 
to 1101h
0
Consistency check selection at
system startup
Set whether to perform consistency
check for controlled axes setting at
system startup.
0: Valid
1: Invalid
Control mode selection
Select the control mode.
0: Standard mode
1: Interface mode
Axis No. assignment
Set 1 when validating axis No.
assignment.
When axis No. assignment is
invalid, axis Nos. are automatically
assigned.
0: Invalid
1: Valid
0003 
 
For manufacturer setting 
 
 
 
0004 SITM 
System 
interrupt 
conditions 
0000h
 
0000h 
to FFFFh
Set the interrupt conditions for the system. 
0005 
 
For manufacturer setting 
 
 
 
0006 0 
0007 0 
0008 0 
0009 0 
000A 0 
000B 0 
000C 0 
000D 0 
000E *EMID 
External 
forced 
stop 
disabled 
0000h
 0000h 
to FFFFh
Disable the forced stop by EMI signal. 
5AE1h 
: Forced stop disabled 
Other than 5AE1h : Forced stop enabled