5. OPERATIONAL FUNCTIONS 
 
5.3 Automatic operation 
5.3.1 Summary 
Automatic operation (positioning) uses the point table for operation. Position data and feed speed designation 
is set in the point table. When the fast start operation signal (FST) is turned on, instructions are executed in 
order from the instruction set at the start point number to the end point number. If automatic operation is 
started prior to completion of home position return (home position return request (ZREQ) is ON), a home 
position return not complete error (operation alarm 90, detail 01) occurs upon starting operation and the 
operation stops. 
 
POINT 
 
The first point number for each of the axis point tables is 0000h. 
The first point number for each of the axis point tables can be designated 
using point number offset. Refer to Section 10.8 concerning point number 
offset. 
 
 
Point table 
Point 
Position data 
[Command units] 
Feed speed 
[Speed units] 
(Note) 
Acceleration time 
constant [ms] 
(Note) 
Deceleration time 
constant [ms]
(Note)
Dwell/pre
dwell [ms]
Auxiliary 
command
Other axes 
start 
specification 
S-curve 
ratio [%]
Reserved
4 bytes 
4 bytes 
2 bytes 
2 bytes 
2 bytes
2 bytes
4 bytes 
1 bytes
11 bytes
0000 2000 
2000 
20 
30 
0 0000h 
00000000h 
0  0 
0001 5000 
2000 
30 
50 
0 0000h 
00000000h 
0  0 
: : 
:  : 
: : : 
Note. Time specified by the acceleration constant, the deceleration constant and the dwell are rounded off based on the control cycle. 
(The value is rounded to the nearest integer.) 
For example, the dwell is specified to 10ms with the control cycle of 0.88ms, the time until executing point is completed after the 
completion of the point movement is 11 control cycles (approx. 9.778ms). 
Speed
0
1
2
0
Positioning complete
(PF)
(Note)
Rough match (CPO)
sscAutoStart function
sscWaitIntDriveFin function/
sscGetDriveFinStatusfunction
Start of operation
Stops after moving
to the end point
position.
Rough match
output limits
(parameter No.
0230, 0231)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Fast Start operation
(FST)
Completion of
operation (OPF)
Automatic operation
mode (AUT)
Operation point number
 
Note. The rough match signal (CPO) is determined when the end point is executed. Therefore, it does not turn on when passing points 
on the way.