1.5.2 Extension Base Power Supply Module
(1) Power supply module specifications
Table 1.5 Power Supply Module Specifications
Specifications
Item
A1S61PN
A1S62PN
Mounting position in base
Power supply module mounting slot
Input power supply
200 to 240 VAC
+10%
-15%
(85 to 264 VAC)
Input frequency
50/60 Hz 
5%
Max. apparent input power
105VA
Rush current
20A 8ms max.
5VDC
5A
3A
Rated output current
24VDC  10%
0.6A
5VDC
5.5 A min.
3.3 A min.
Overcurrent protection *
1
24VDC
0.66 A min.
5VDC
5.5 to 6.5 V
Overvoltage protection *
2
24VDC
Efficiency
65% min.
Withstand voltage
2,830VAC rms/3 cycles across all inputs/LG and all outputs/FG (altitude 2,000m
(6557.38 ft))
Insulation resistance
5M
 or more by 500VDC insulation resistance tester across all inputs/LG and all
outputs/FG
Noise immunity
(1) By noise simulator of 1,500Vp-p noise voltage, 1 s noise width and 25 to
60Hz noise frequency
(2) Noise voltage IEC801-4, 2kV
Power indicator
LED indicator
Terminal screw size
M3.5
7
Applicable power cable size
0.75 to 2mm
2
Applicable solderless terminal
RAV 1.25-3.5    RAV 2-3.5
Applicable tightening torque
59 to 88 N
cm
External dimensions mm (inch)
130
54.5
93.6 (5.12
2.15
3.69)
Weight kg (lb)
0.6 (1.32)
Permissible instantaneous power interruption time
20ms max.
POINT
*1: Overcurrent protection
When current in excess of the specifications flows through the 5 VDC or
24 VDC circuits, the overcurrent protection device breaks the circuit and
stops the system.
A drop in voltage will extinguish or dim the power supply module
indicator “POWER” display.
After overcurrent protection operates, start up the system after
eliminating the cause, such as insufficient current capacity or short
circuit.
The system initial start commences when the current returns to the
normal level.
*2: Overvoltage protection
When an overvoltage of 5.5 V to 6.5 V is applied to a 5 VDC circuit, the
overvoltage protection device breaks the circuit and stops the system.
The power supply module indicator goes out.
To restart the system, switch the input power supply off, and then turn it
back on. The system initial start commences.
If the system does not start up and the indicator “POWER” display
remains off, the power supply module must be changed.