Magellan MG-6060 ユーザーズマニュアル

ページ / 48
Paradox Magellan Systems
 
21
One-Touch Arming
Section [092]: Options [7] and [8]
Option [7] OFF = One-touch Regular/Force arming disabled
Option [7] ON =
One-touch Regular/Force arming enabled 
(default)
Option [8] OFF = One-touch Stay arming disabled
Option [8] ON =
One-touch Stay arming enabled (default)
The One-touch arming features allow users to arm the system 
without having to enter any access codes. To arm the system, 
press and hold the appropriate key for approximately 2 seconds.
Exit Delay
Section [062]: 001 to 255 seconds; 000 = disabled; Default = 60 
seconds
The exit delay determines the amount of time a user has to leave 
the protected area before Magellan arms the system. The exit 
delay applies to all zones (except 24Hr zones) in the system. 
Program the exit delay from 001 to 255 seconds.
Bell Squawk on Arm/Disarm with Remote 
Control
Section [093]: Option [3]
Option [3] OFF = Bell squawk disabled
Option [3] ON =
Bell squawk enabled (default)
When option [3] is enabled (ON), the siren will squawk once 
upon arming with a remote control and twice upon disarming with 
a remote control.
No Exit Delay when Arming with Remote 
Control
Section [093]: Option [4]
Option [4] OFF = Provides exit delay when arming with remote 
control (default)
Option [4] ON =
No exit delay when arming with remote control
When option [4] is enabled (ON), the console cancels the Exit 
Delay (arms instantly) when the system is armed with a remote 
control. When disabled, the Exit Delay timer will start when the 
system is armed with a remote control.
Exit Delay Termination
Section [093]: Option [6]
Option [6] OFF = Exit delay termination feature disabled
Option [6] ON =
Exit delay termination feature enabled (default)
When option [6] is enabled (ON), the console will reduce the exit 
delay to 10 seconds when an Entry Delay zone (see Exit Delay 
on page 21) is opened and closed during the exit delay.
Example: 15 seconds into a 45 second exit delay, an Entry Delay 
zone opens and closes. The remaining 30 seconds is reduced to 
10 seconds.
Follow Zone Switches to Entry Delay 2
Section [093]: Option [7]
Option [7] OFF = Follow zone triggers an alarm (default)
Option [7] ON =
Follow zone follows Entry delay 2 when 
opened
When option [7] is enabled (ON) and an Entry Delay 1 zone is 
bypassed, an armed Follow zone that opens without an entry 
delay being triggered will switch to the entry delay 2 timer.
Example: Zone 1 is an Entry Delay zone and zone 2 is a Follow 
zone protecting the area where the keypad is installed. The 
system is armed but zone 1 is bypassed. With option [7] 
enabled, zone 2 will switch to and wait for the entry delay 2 timer 
to elapse before triggering an alarm.
Closing Delinquency Timer
Section [080]: 001 to 255 days; 000 = Disabled; Default = 000
The Magellan console will verify when the system was last 
armed at midnight of every day. If the last time the system was 
armed is greater than the programmed Closing Delinquency 
timer, the console will transmit a Closing Delinquency report 
code (page 25) to the central monitoring station. 
Enter a value from 001 to 255 days into section [080] to program 
the Closing Delinquency timer. Enter 000 to disable the timer.