SPX Cooling Technologies 800 ユーザーズマニュアル

ページ / 28
     
1
Temperature Control and Energy 
Management
The  wet-bulb  temperature  of  the  ambient  air  varies  significantly  on  a 
daily basis, and considerably from season to season. As the wet-bulb 
temperature reduces, the tower becomes capable of producing colder 
and colder water—or it becomes capable of producing a given cold water 
temperature at reduced airflow through the tower. These characteristics 
are the “opposing forces” referred to on page 4.
Maximizing Tower Performance
If your operating system is one which benefits from the coldest possible 
water; that is, if colder water allows you to increase your output—or allows 
you to operate your system at significantly lower cost, then continuous full 
speed operation of the fan(s) may be your best mode of operation.  
In this mode of operation, concern for the cold water temperature level 
would be limited to the potential for the tower to form ice during freezing 
weather. (See 
Caution note on page 8 and Freezing Weather Operation 
on pages 11 and 12.) Although the 70°F (21°C) cold water temperature 
indicated on page 11 is appropriate for cold weather start-up and operation, 
acceptable temperatures during full operation in spring, summer, and fall 
may be appreciably lower, perhaps as low as 50°F (10°C) or less. 
Refer to 
your performance curves for expected tower cold water temperatures 
at varying flow rates, ranges, and wet bulb temperatures.
Minimizing Tower Energy Use
Most systems gain no operating or production benefits from water tem-
peratures below a certain level, and that level is not usually below the 
aforementioned 70°F (21°C). When a reducing ambient wet-bulb permits 
the tower to reach that target cold water temperature level, further reduc-
tions in the wet-bulb temperature permit manipulation of fan speeds or 
operation to maintain that temperature level.
Single-speed fans can be cycled on and off for cold water temperature 
control, with the steps of control depending upon the number of fan cells 
in the tower. Two-speed motors offer twice as many control steps—with 
the added bonus that half-speed (which produces half of the normal air-
flow through the tower) requires less than 20% of the full-speed power 
requirement.
Excessive cycling of motors causes overheating of the windings and 
ultimate failure of the motor. The total amount of starting time (period 
of high inrush current) should not exceed 0 seconds per hour. On 
fans 0 feet diameter and smaller, this may allow  or  starts per hour. 
On larger fans, 1 or  starts per hour may be the limit.  Determine the 
 
 Note
 
 Caution