SPX Cooling Technologies 800 ユーザーズマニュアル

ページ / 28
0         
Seasonal Shutdown Instructions
Tower
Drain all tower piping.
During shutdown, clean the tower and make any necessary repairs. Ap-
ply protective coating as required to all metal parts. Particular attention 
should be given to mechanical equipment supports, drive shaft and drive 
shaft guards, Geareducers, and motors.
See Warning note on page 1 regarding tower cleaning.
Visually inspect for concrete deterioration. If ambient temperature is 32°F 
(0°C) or below, do not put cold water on tower.
Mechanical Equipment
Shutdown for less than  months.
Each month, drain water condensate from the lowest point of the Geareduc-
er and its oil system. Check oil level and add oil if necessary. Operate 
Geareducer briefly to recoat all interior surfaces with oil. At start-up, drain 
water condensate and check oil level. Add oil if necessary.
Refer to 
Geareducer Service Manual for maintenance and lubrication 
instructions.
Shutdown for  months or longer.
If the motors have space heaters, operate mechanical equipment one hour 
each month.  Space heaters should be energized anytime motor is not 
operating. If the motors do not have space heaters, operate mechanical 
equipment one hour each week. At start-up, operate mechanical equip-
ment one hour or until oil is warm, then shut the equipment down. Drain 
the oil and refill with new oil.
Refer to 
Geareducer Manual for instruction on changing oil. Refer to Marley 
Downtime Instruction Manual for downtime of 6 months or longer.
Electric Motors
Do not start motor without determining that there will be no interfer-
ence with free rotation of the fan drive. Refer to Marley Electric Motor 
Service Manual.
If shutdown period is longer than seasonal, contact your Marley sales 
office or representative for additional information.
 
 Caution