Honeywell F111 Series 1 ユーザーズマニュアル

ページ / 10
F111 (SERIES 1,2) IN CEILING MEDIA AIR CLEANER
3
68-0198EF-4 Rev. 11-07
Approvals:
Underwriters Laboratories Inc.: Listed. 
Canadian Standards Association: Listed.
Accessory: 32000234 Variable Speed Switch.
Replacement Parts See Parts List, Table 4.
PLANNING THE INSTALLATION
The number of F111 (series 1,2) air cleaners that are needed is 
determined by taking into account the number of occupants 
and the volume of the space. Type of contamination, outdoor 
air quality and use of the area are also factors. Refer to Table 
3 for general guidelines when determining how many air 
cleaners are needed.
EXAMPLE: One air cleaner can provide 2.5 air changes per 
hour in a 24,000 cubic feet (720 cubic meters) no 
smoking area. Table 3 suggests two air cleaners 
for a 24,000 cubic feet area because most areas 
have contaminants that require more units to
 provide quality air.
If any questions should arise concerning determining the 
number of air cleaners needed for an area, consult your 
distributor or local Honeywell Commercial Air Cleaner 
Distributor.
Table 3. Determining the Minimum Number of
Air Cleaners Needed for a Space.
WARNING
TO REDUCE THE RISK OF FIRE,ELECTRICAL 
SHOCK, OR INJURY TO PERSONS,OBSERVE THE 
FOLLOWING:
1.
Installation Work And Electrical Wiring Must Be Done 
By Qualified Person(s) In Accordance With All Applica-
ble Codes And Standard, Including Fire Rated Con-
structions.
2.
When Cutting Or Drilling Into The Wall Or Ceiling, Do 
Not Damage Electrical Wiring And Other Hidden Utili-
ties.
3.
Never Place A Switch Where It Can Be Reached From 
A Tub Or Shower.
4.
Use This Unit Only In The Manner Intended By The 
Manufacturer. If You have Questions, Contact The Man-
ufacturer.
5.
Before Servicing Or Cleaning Unit, Switch Power Off At 
Service Panel And Lock Service Panel To Prevent 
Power From Being Switched on Accidentally.
6.
If This Unit Is To Be Installed Over A Tub Or Shower, It 
Must Be Marked As appropriate For The Application.
Choose Location
Choosing the correct location for the air cleaner affects the 
overall performance of the unit. The bidirectional airflow 
pattern must flow into the longest reaches of the zone being 
cleaned. See Fig. 2.
Fig. 2. Correct positioning of the air cleaner 
for optimum cleaning.
NOTE: The F111 Has Not Been Investigated 
For Use In Fire Resistance Rated 
Construction.
The air cleaner is designed to be suspended centrally in a 
space and mounted into or on a ceiling. The cleaning footprint 
of the air cleaner is rectangular with air patterns that move 
clean air to the corners of the area while drawing contaminated 
air up from the center of the area. See Fig. 2.
When multiple air cleaners are installed, the allotted areas to 
be cleaned should be equal. The air throw in one direction is 
approximately 55 ft (17m). Air velocity at 90 ft per minute 
(27m per minute) is considered end of throw.
IMPORTANT
Never hang the air cleaner higher than 16 ft (5m) 
above the floor.
Space Volume 
 (L x W x H) in Cubic 
Feet (Cubic Meter)
Number of 
Persons Present
Minimum 
Number of Air 
Cleaners
12000 to 18000 
(360 to 540)
30 to 60
1
18001 to 35000 
(540 to 1050)
61 to 90
2
35001 to 51000 
(1050 to 1530)
91 to 120
3
51001 to 65000 
(1530 to 1950)
121 to 180
4
65001 to 80000 
(1950 to 2400)
181 to 240
5
80001 to 95000 
(2400 to 2850)
241 to 300
6
F111
(SERIES 
11000)
CLEANING FOOTPRINT
CEILING
FLOOR
CORRECT
2
1
INCORRECT
M12652A