Macurco DVP-120 ユーザーズマニュアル

ページ / 37
Revision 0.07 
22 
3.3.2.2  Set Day of Week 
T  i  m e  :    2  2  :  5  5           
D a  y  :  2    T  u  e  s  d  a  y       
Figure 3-19 Set Day of the week 
This display example shows that Tuesday is the current day of the week. The underline character indicates that 
the day can be changed by entering the corresponding digit: 
– 
Monday 
– 
Tuesday 
– 
Wednesday 
– 
Thursday 
– 
Friday 
– 
Saturday 
– 
Sunday 
 
3.3.2.3  Load Default Configuration 
1    L  o  a  d    D e  f  a  u  l  t     
    C o  n  f  i  g  u  r  a  t  i  o  n   
Figure 3-20 Load Default Configuration 
When the one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously. 
If the password is entered  correctly, the panel will  overwrite the existing configuration with the default 
configuration. This operation is intended to restore the panel to a known basic condition if it is removed from 
one installation and installed in another.  
 
The default configuration is: 
?
 
Password 
1234 
?
 
Sensors  
Undefined 
?
 
Alarm levels 
CO = 200 ppm, HS = 5.0ppm, EX = 4,000 ppm 
?
 
Alarm signals 
Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous 
?
 
Warning signals 
Buzzer = Double Tap, Horn = Off, Strobe = Off 
?
 
Trouble signals 
Buzzer = Triple Tap, Horn = Off, Strobe = Off 
?
 
Warning Levels 
CO = 200 ppm, HS = 5.0 ppm, EX = 4,000 ppm 
?
 
Sensor Range 
CO = 200ppm, HS = 6.0 ppm, EX = 10,000 ppm 
?
 
Relay 1 
Normally off, 1 minute turn on delay, 1 minute minimum on time 
?
 
Relay 2 
Normally off, 1 minute turn on delay, 1 minute minimum on time 
?
 
Relay 3 
Normally off, 1 minute turn on delay, 1 minute minimum on time 
?
 
Horn 
Normally off, 1 minute turn on delay, 0 (zero) minimum on time 
?
 
Strobe 
Normally off, 1 minute turn on delay, 0 (zero) minimum on time 
?
 
Zone1 
Controls nothing, no sensors assigned, Voting mode, Quorum = 1 
?
 
Zone2 
Controls nothing, no sensors assigned, Voting mode, Quorum = 1 
?
 
Zone3 
Controls nothing, no sensors assigned, Voting mode, Quorum = 1 
?
 
Rising Trip Levels  CO = 100 ppm, HS = 2.5ppm, EX = 2,000 ppm 
?
 
Falling Trip Levels  CO =   50 ppm, HS = 1.2 ppm, EX = 1,000 ppm