Clearances
Unless otherwise stated the clearances listed below are Minimum 
distances to combustible materials.  Please Note: A major cause 
of chimney related fi res is due to a failure to maintain required 
clearances (air space) to combustible materials. It is of the greatest 
importance that this fi replace and vent system be installed only in 
accordance with these instructions.
Combustible Mantels
Because of the extreme heat this fi replace emits, the mantel 
clearances are critical.
 Combustible mantel clearances from top of 
the louvers are shown in the diagram below. Mantel may be installed 
anywhere in the shaded area or higher.
Note:  A non-combustible mantel may be installed at a lower 
height.
Note:  Ensure the paint that is used on the mantel and the facing 
is “heat resistant” or the paint may discolour.
G
H
I
A
D
B
E
F
C
Clearances to Combustibles
Dimension
Description
U31
A
From Unit to Sides
10” (254mm)
B
From Unit to Ceiling
47-1/2” (1207mm)
C
From Unit to Mantel
see mantel clearances
D
From Standard Surround to Sides
4” (102mm)
E
From Standard Surround to Ceiling
41-1/2” (1054mm)
F
Minimum Mantel Height
13” (330mm)
G
Maximum Mantel Depth
12” (305mm)
H
Minimum Alcove Width
48” (1219mm)
I
Maximum Alcove Depth
36” (914mm)
*No Hearth Required
Clearances when installed with a Zero Clearance Kit
Dimension
Description
U31
F
Minimum Mantel Height
20” (508mm)
G
Maximum Mantel Depth
11-1/2” (292mm)
NOTE:  Mantel clearances for Installation into a Zero Clearance Kit 
are different. Please refer to the Zero Clearance Kit Manual 
for details.
U31 Regency Gas Insert
120
August 2008 Product Specifi cations Book