 E21-3 Gas Fireplace Insert
TEST FOR 
FLUE SPILLAGE
A " spillage" test must be made before 
the installed unit is left with the customer.  
Follow the procedure below:
1)  Close all external doors and windows in 
the house.
2)  Light the unit and set controls to maximum. 
Turn fan to OFF on unit.
3)  After fi ve minutes, test that there is a “pull” 
on the fl ue by placing a smoking match, 
cigarette or similar device which gives 
off smoke, in front of the upper part of 
the louver. To ensure a valid test, place 
GAS INSERT  
AERATION SYSTEM
The aeration adjustment rod is attached to the 
air shutter which is located just above the orifi ce 
bracket. The rod is used to adjust the aeration 
on the main burner without having to take the 
appliance apart. 
The burner aeration is factory set but may need 
adjusting due to either the local gas supply, air 
supply or altitude. 
 
Natural Gas:  1/8" open
 Propane: 
5/16" 
open
Note:   Any damage due to carboning 
resulting from improperly setting 
the aeration controls is NOT covered 
under warranty.
Note:  Aeration Adjustment should only be 
performed by an authorized Regency
®
 
Installer at the time of installation or 
service.
a scrap piece of sheet metal (or other 
noncombustible material) in the upper louver, 
this will prevent the natural convection of the 
unit from interfering with the test.
Note:  The smoke should be drawn into the 
louver. If the smoke is still not drawn 
in, turn the unit off and check for the 
cause of the lack of draft.  If necessary, 
seek expert advice. 
OPTIONAL 
BRICK PANEL
1)  Unwrap the brick pattern panels from the 
protective wrapping.
2)  With the glass removed, position the 
back panel fi rst (see diagram for correct 
positioning), then the two side panels. Slide 
the side brick panel into place from the front 
of the fi rebox, there is a tab at the top of the 
unit to hold the side panels in place. 
3)  The brick panels should be tight against 
the fi rebox sides and back. The side panels 
should be fl ush with the glass.
Note:  Use caution when sliding side panels 
in as they can easily be scratched by 
the brick panel tabs.
VALVE DESCRIPTION
1)  Gas on/off knob
2)  Manual high/low adjustment
3) Pilot 
Adjustment
4) Thermocouple Connection
5) Main Operator
6)  Outlet Pressure Tap (Manifold Pressure)
7)  Inlet Pressure Tap (Supply Pressure)
8) Pilot Outlet
9)  Main Gas Outlet
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit
13) Additional Valve Mounting Hole
INSTALLATION