Hearth & Home Technologies 3100-I ユーザーズマニュアル

ページ / 28
Page 5
 
September 1, 2008  
3100-I ACT WOOD INSERT
 250-638D
Hearth Extension 
A
B
C
D
F
E
Insert
Side
W
all
 
Maximum Mantel Depth - 10" (254mm) 
Fascia or Trim 
Mantel 
Thermal Protection USA & Canada 
 
 
 
 
 
USA
   
CANADA
A  Sidewall to Stove 
 
16" 
16" (406mm)
B  Mantel Clearances
 
*No Mantel Shield 
 
 33"  34" (864mm)
 
with 5" Mantel Deflector 
 27"  24" (610mm)
 
with 8" Mantel Deflector 
 17"  16"(406mm)
 
with Mantel Shield Only 
 24"  18"(457mm)
 
5" Deflector & Mantel Shield 
 23"  15"(381mm)
 
8" Deflector & Mantel Shield 
 15"  15"(381mm)
C   Top Trim to Stove
 
*No Mantel Shield 
 
 30"  30" (762mm)
 
with 5" Mantel Deflector 
 23"  21" (533mm)
 
with 8" Mantel Deflector 
 16"  14"(356mm)
 
with Mantel Shield Only 
 22"  14"(356mm)
 
5" Deflector & Mantel Shield 
 15"  14"(356mm)
 
8" Deflector & Mantel Shield 
 12"  14"(356mm)
D  Side Trim to Stove   
   6"   6" (152mm)
E  Hearth Extension-Front
 
Floor height 0" to 8" below Insert  18"  18" (457mm)
 
Floor height greater than 8"  
 16"  18"(457mm)
F  Hearth Extension-Side  
8" 
  8" (203mm)
*Zero Clearance Installations USA Only
Thermal protection must be  ('k" value = 0.84) or equivalent material*
Floor height 0" to 8" below Insert  1 Inch (12.7mm) of "k" = 0.84
Floor height greater than 8"   
1/2 inch (25mm) of "k" = 0.84
NOTE:  When installing into a masonry fire-
place,  the  fireplace  must  be  built  to  UBC 
Chapter 37 standards.  Do not remove brick 
or mortar from masonry fireplace to accom-
modate insert.  The permanent metal warn-
ing plate provided must be attached to the 
back  of  the  fireplace  stating  the  fireplace 
may have been altered to accommodate the 
insert and must be returned to original con-
dition for use as a conventional fireplace.
CLEARANCES TO COMBUSTIBLES
United States and Canada
*
See Alternative Floor Protection Worksheet on 
page 7.
The Mantel Shield must be comprised of a non-combustible mate-
rial  located  a  minimum  of  1”  (25mm)  from  mantel’s  under  side 
extending to the full width of the mantel.  The Mantel Deflector’s 
are available from your dealer.
In Canada a full length 6” (152mm) S635 
flue liner required as per ULC S628.