3100-I ACT WOOD INSERT
 250-638D
MASONRY FIREPLACE 
USING DIRECT-CONNECT METHOD
Refer to: Clearances to Combustibles on page 5,  Canadian Installation requirements on page 11,  
Hearth Requirements on page 5 and Zero Clearance Adjustable Support Kit on page 14.
Figure 9A - Installation Into Masonry Fireplace
Direct Connect 
  Seal Option
Minimum Starter
   
 Pipe Option
Full Listed 
Liner Option
Masonry Chimney
Flue Tile 
Mantel
Air-tight Face Seal
Damper Area
SEAL DAMPER AREA OR FACE SEAL
INSTALLATION OPTIONS
The  Quadra-Fire  3100-I ACT  Insert  conforms  with  the  UL 
Standard  for  Safety  1482  and  ULC  S628  (Canada)  in  all 
respects,  and  is  approved  to  UL  &  ULC  safety  standards 
for  installation  and  use  within  a  fireplace  with  a  masonry 
chimney in accordance with NFPA No. 211, with or without 
a direct flue collar connection.  A starter pipe is required to 
reach to the bottom of the existing flue. 
1.  Secure the fireplace damper in the open position.  If this 
cannot be accomplished, it will be necessary to remove the 
damper.
.  Seal the damper area around the chimney liner with a 
high temperature sealant.
3.  The chimney should be examined for cracks, loose mortar, 
and  other  signs  of  deterioration  and  blockage.   The  insert 
should not be installed until it is determined that the chim-
ney is safe for use.  Since an oversized flue contributes to 
the accumulation of creosote, the size of the flue should be 
checked to determine that it is not too large for the insert.  
The chimney should also be checked to ensure it meets the 
minimum standard of the National Fire Protection Associa-
tion (NFPA) Standard 211.  The following bullets list the more 
critical requirements for a properly constructed chimney:
 
•  The  masonry  wall  of  the  chimney,  if  brick  or  modular 
block,  must  be  a  minimum  of  4  inches  (102mm)  nominal 
thickness.  A chimney of rubble stone must be at least 12 
inches (305mm) thick
 
 The chimney must have a fire clay flue liner (or equiva-
lent) with a minimum thickness of 5/8” (16mm) and must be 
installed with refractory mortar.  An equivalent liner must be 
a listed chimney liner system or other approved material.
 
 A chimney inside the house must have at least  inches 
(51mm) of clearance to the combustible structure.  A chim-
ney  outside  the  house  must  have  at  least  1  inch  (25mm) 
clearance to the combustible structure.  Non-combustible fire 
stops  must  be  installed  at  the  spaces  where  the  chimney 
passes through floors and/or ceiling 
(See Figure 8A and 8B 
on page 8)
NOTE:  In Canada, a full reline is required.
METAL HEAT CIRCULATING MASONRY
The Quadra-Fire 3100-I Insert conforms with the safety stan-
dard UL-1482 and ULC S628 (Canada) in all respects and is 
approved to UL & ULC safety standards for installation and 
use within a fireplace with masonry chimney, in accordance 
with NFPA No. 211, with or without a direct flue collar con-
nection.  A starter pipe is required into existing chimney.
Figure 9B
 - 
Installation Into Metal Heat Circulating 
Showing Use Of Starter Pipe
Listed Liner
Mantel
SEAL DAMPER AREA OR FACE SEAL