Hearth & Home Technologies 4100I-GD-B ユーザーズマニュアル

ページ / 28
4100-I  ACT WOOD INSERT
Page 10
   September 1, 2008
R
250-7201E
MASONRY FIREpLACE 
USING DIRECT-CONNECT METHOD
Refer to: Clearances to Combustibles on page 5,  Canadian installation requirements on page 12,  
Hearth Requirements on page 5 and Zero Clearance Adjustable Support Kit on page 16.
Figure 10A - installation into Masonry Fireplace 
Direct Connect 
  Seal Option
Minimum Starter
   
 Pipe Option
Full Listed 
Liner Option
Masonry Chimney
Flue Tile 
Mantel
Air-tight Face Seal
Damper Area
SEAL DAMpER AREA OR FACE SEAL
INSTALLATION OpTIONS
This  product  conforms  with  the  UL  Standard  for  Safety 
1482 (USA) and ULC S628 (Canada) in all respects, and 
is approved to UL & ULC safety standards for installation 
and use within a fireplace with a masonry chimney in accor-
dance with NFPA 211, with or without a direct flue collar con-
nection.  A starter pipe is required to reach to the bottom of 
the existing flue. 
1.  Secure the fireplace damper in the open position.  If this 
cannot be accomplished, it will be necessary to remove 
the damper.
2.  Seal  either  the  damper  area  around  the  chimney  liner 
with a high temperature sealant or the fireplace front with 
fiberglass batting.
.  The  chimney  should  be  examined  for  cracks,  loose 
mortar,  and  other  signs  of  deterioration  and  blockage.  
The  insert  should  not  be  installed  until  it  is  determined 
that the chimney is safe for use.  Since an oversized flue 
contributes to the accumulation of creosote, the size of 
the flue should be checked to determine that it is not too 
large for the insert.  The chimney should also be checked 
to ensure it meets the minimum standard of the National 
Fire  Protection Association  (NFPA)  Standard  211.   The 
following bullets list the more critical requirements for a 
properly constructed chimney:
•  The  masonry  wall  of  the  chimney,  if  brick  or  modular 
block, must be a minimum of 4 inches (102mm) nominal 
thickness.  A chimney of rubble stone must be at least 12 
inches (05mm) thick
•  The chimney must have a fire clay flue liner (or equiva-
lent) with a minimum thickness of 5/8” (16mm) and must 
be  installed  with  refractory  mortar.   An  equivalent  liner 
must be a listed chimney liner system or other approved 
material.
•  Cross-sectional area should be no more than  times the 
cross-sectional area of the flue collar of the insert.  (28 sq 
inch flue area x  inches = 84 square inches maximum 
chimney area).
•  A chimney inside the house must have at least two inches 
(51mm) of clearance to the combustible structure.  A chim-
ney outside the house must have at least 1 inch (25mm) 
clearance to the combustible structure.  Non-combustible 
fire stops must be installed at the spaces where the chim-
ney passes through floors and/or ceiling 
(See Figure 8A 
and 8B on page 8)
NOTE:  In Canada, a full reline is required.
METAL HEAT CIRCULATING MASONRY
This  product  conforms  with  the  safety  standard  UL1482 
(USA)  and  ULC  S628  (Canada)  in  all  respects  and  is 
approved to UL & ULC safety standards for installation and 
use within a fireplace with masonry chimney, in accordance 
with NFPA 211, with or without a direct flue collar connec-
tion.  A starter pipe is required into existing chimney.
 
Figure 10B 
installation into Metal Heat Circulating
Showing Use Of Starter Pipe
Listed Liner 
Mantel 
SEAL DAMpER AREA OR FACE SEAL