Hearth & Home Technologies 4100I-NL-B ユーザーズマニュアル

ページ / 28
4100-I  ACT WOOD INSERT
Page 6
   September 1, 2008
R
250-7201E
AVOID FIRE:  To ensure that insulation or any other com-
bustible material does not contact the chimney, a chimney 
inside the house must have at least 2 inches (51mm) of air 
space  clearance  around  the  chimney.   A  chimney  outside 
the house must have at least one inch (25mm) clearance 
to  the  combustible  structure.    Noncombustible  fire  stops 
must be installed at the spaces where the chimney passes 
through floors and/or ceilings.  
Refer to Figures 8A & 8B 
on page 8.  Canadian installations require a full reline of 
the chimney
CHIMNEY HEIGHT/DRAFT
To be sure that your Quadra-Fire insert burns properly, the 
chimney  draft  (static  pressure)  should  be  approximately 
-0.10” water column (W.C.) during a high burn and -0.04” 
W.C. during a low burn, measured six inches (152mm) above 
the top of the insert after one hour of operation at each burn 
setting.
NOTE:  These are guidelines only, and may vary somewhat 
for individual installations.
The insert was designed for and tested on a six inch (152mm) 
chimney, 12 ft-14 ft (60-420cm) high, measured from the 
base of the insert.  The further your stack height or diameter 
varies from this configuration, the possibility of performance 
problems increases.  In addition, exterior conditions such as 
roof line, surrounding trees, prevailing winds and nearby hills 
can influence insert’s performance.
A masonry chimney or a listed factory-built UL10 HT Class 
“A”  chimney  must  be  the  required  height  above  the  roof 
and any other nearby obstructions.  The chimney must be 
at least  ft (91cm) higher than the highest point where it 
passes through the roof and at least 2 ft (61cm) higher than 
the highest part of the roof or structure that is within 10 ft 
(05cm) of the chimney, measured horizontally.  
See 2-10-3 
Rule (Figure 6A).  These are safety requirements and are 
not meant to assure proper flue draft.
ft Min 
(91cm) 
2 ft Min (61cm) 
10 ft Min 
(05cm) 
2-10-3 RULE 
Figure 6A
NOTE: Clearances may only be reduced by means approved 
by the regulatory authority having jurisdiction.
WE RECOMMEND that a qualified building inspector and 
your insurance company representative review your plans 
before and after installation.
INSTALLATION RECOMMENDATIONS
These installation instructions describe the installation and 
operation of the Quadra-Fire 4100-I Wood Insert.  This insert 
meets  the  U.S.  Environmental  Protection Agency’s  1990 
particulate  emission  standards.   This  product  is  listed  by 
OMNI-Test Laboratories, Inc. to UL Safety Standard 1482, 
and ULC S628, and (UM) 84-HUD. This insert is approved 
for mobile home installations when not installed in a sleeping 
room and when an outside combustion air inlet is provided.  
The  structural  integrity  of  the  mobile  home  floor,  ceiling, 
and walls must be maintained.  The insert must be properly 
grounded to the frame of the mobile home.  
Check with your local building code agency before you begin 
your  installation  to  ensure  compliance  with  local  codes, 
including  the  need  for  permits  and  follow-up  inspections.  
Be sure local building codes do not supersede UL specifica-
tions and always obtain a building permit so that insurance 
protection  benefits  cannot  be  unexpectedly  cancelled.    If 
any assistance is required during installation, please contact 
your local dealer.
LISTINGS
CHIMNEY HEIGHT/DRAFT 
(CONT’D)
This product has met and surpassed the most stringent emissions 
standards in the United States.  The sophistication of the interior 
firebox design requires that a proper draft be supplied by the chim-
ney, therefore adherence to the following factors will enable your 
insert to operate at its optimum capability.
REqUIRED:  A minimum NFPA 211 required stainless steel 
liner  connector  pipe  extending  to  the  first  flue  liner  of  the 
existing code approved masonry chimney.  To eliminate dilu-
tion air in the chimney, seal the damper area of the chimney 
around the chimney connector.
BEST:  A complete relining of the chimney system with a six 
inch (152mm) diameter listed, stainless steel liner.  The liner 
must  be  connected  to  the  insert  flue  collar  and  extend  the 
entire height of the chimney, terminating slightly above a plate 
that seals the top of the chimney. All joints should be secured 
with  sheet metal screws. The sections must be attached to 
the insert and to each other with the crimped (male) end point-
ing toward the insert.  
Figure 6B.
Minimum clearances to combustibles must be maintained.
A full reline is required for factory-built fireplace installations in 
Canada and is highly recommended in USA. 
LINER CONNECTOR
FLUE
 GAS 
DIRECTION
CRIMPED 
END 
TOWARDS 
STOVE
Figure 6B