Hearth & Home Technologies 2700-I ユーザーズマニュアル

ページ / 28
Page 7
 
September 1, 2008
7007-161H
2700-I  WOOD INSERT (ACT)
Floor
Ceiling
Caulk
       
Floor
(second Story)
Non-Combustible
Firestopping
Material
Minimum 1 inch (25mm) 
clearance from exterior 
chimney to sheathing
Firestopping
2 inch 
(51mm)
CHIMNEY REqUIREMENTS 
Non-combustible
fire stopping material
Minimum 2 inch (51mm) clearance
from combustible material
and insulation
ceiling
At least 2 ft
(61cm)
At least ft
(91cm)
CHIMNEY HEIGHT
10 ft
(05cm)
CHIMNEY TOp VIEW
FLUE
Foundation
1/2" (12.7mm) airspace
5/8" (16mm) 
Fireclay Flue 
Liner
Chimney Wall 
4" (102mm) 
Nominal
Figure 7.1
OVALIZING ROUND STAINLESS STEEL 
LINERS 
Ovalizing round stainless steel liners to accommodate the 
liner passing through the damper region of a fireplace is an 
allowable and acceptable practice.
Ensure  that  the  ovalization  is  minimized  to  the  extent 
required to fit through the damper.
Figure 7.3 - 2-10-3 Rule
Figure 7.2
Figure 7.4
WARNING
ONLY use connector:
•  Within the room, between appliance and ceiling or wall.
Connector shall NOT pass through:
•  Attic or roof space
•  Closet or similar concealed space
•  Floor or ceiling
Maintain minimum clearances to combustibles
Fire Risk.
Follow Chimney Connector Manufacturer’s 
Instructions for Proper Installation.
WARNING
•  ALWAYS maintain specified clearances around venting and 
spacers.
•  Install spacers as specified.
     Failure to keep insulation or other material away from vent 
pipe may cause fire.
Fire Risk.
Do NOT pack insulation or other combustibles 
between spacers.