Caused by (outdoor unit)
LED lamps
Meaning
2   3   4   5
— Normal
●    ●
●    ●
●    ●
Normal operation
— Defective in IC chip (E
2
PROM)
●    ●
●    ●
●   
Cannot read IC chip data or missing IC chip on outside 
PCB
— Defective Gas Valves
● ●
Detects abnormality in Gas Valve Circuit at initial 
checking
A
Detective Thermistor 1
● ●
● ●
Open or Short of Thermistor 1
B
Detective Thermistor 2
● 
●    ●
Open or Short of Thermistor 2
C
Limit switch
● 
●   
Thermal fuse or Bimetal Thermostat tripped
D
Flame current circuit
● ●
Defective abnormal in Flame Current Circuit
E
Lighting failure
● ● ●
Couldn’t establish flame
F
Lost flame
● 
● ●
●    ●
Flame Sensor Circuit detects lost flame and could not 
establish the flame
G
Incorrect combustion motor speed
● 
● ●
●   
Incorrect combustion motor speed
H
Over-time period in retry
● 
Thermistor 1 or Thermistor 2 temperature did not go 
down in set period
I
Over number of times in retry
● 
● ●
Combustion stopped by Thermistor 1 or Thermistor 2 
more than set number
J
Bypass Valve (V2) not open
● ● 
●    ●
Bypass Valve failure or drop-out of Thermistor 2
— Reversing Valve not working
● ● 
●   
Reversing Valve failure, drop-out of Thermistor 2, or 
shortage of refrigerant
12-3-2.  Thermistor Abnormality (Indoor Unit Only)
Check open / short circuit at the coil thermistor and room thermistor (between 1 and 2 of the lamp 8P) on the
PCB of the indoor unit (but only when the room temperature is 14 to 113°F).
12-3-3.  Protective Circuit of Outdoor (Burner) Unit Operated
Check the following according to the failure display. Check items listed in 12-6. Heating Operation Not Possible.
12-3-4.  CT Detection (Refer to 12-3-9 and 12-3-10.)
(1) Compressor abnormality
(2) Compressor over-load relay engaged
Note: Refer to 12-8. Failure Display on Outdoor Unit and Correction Method.