Sanyo KGS1411 ユーザーズマニュアル

ページ / 100
60
12-6-3.  Safety Device Operated
Failure Display on Outdoor Unit PCB: 
● 
●  
Check safety device.
Disconnect safety device connector (CN12, 2P, WHT) from outdoor unit PCB, and measure resistance on the
safety device.
In case of abnormality 
Replace temperature fuse or temperature limiting switch.
Normal
Ω
or less
*
Use a circuit tester (set to 
Ω
range).
In case of abnormality 
Replace outdoor unit PCB.
In case of abnormality 
Replace outdoor PCB.
Remove flame rod connector, and measure direct current between connector and PCB.
Caution: The flame rod retains electromotive force immediately after combustion ceases, therefore measure-
ment should be made while the equipment is cool.
12-6-4.  Erroneous Flame Detection
Failure Display on Outdoor Unit PCB: 
● ●
Check flame sensor probe.
Measure voltage of alternative current between flame rod connector (1P, CN17) and ground.
Normal
AC 104 – 126 V
Normal
DC 1µA or less
*
Use a circuit tester (set to AC range).
*
Use a circuit tester (set to DC range).
Normal
AC 104 – 126 V
12-6-5.  Ignition Failure
Failure Display on Outdoor Unit PCB: 
● ● ●
1) Check ignition transformer.
Check if ignition wires are disconnected or have voltage leak.
Measure AC voltage between the connectors (CN07) to the ignition electrode.
In case of abnormality 
Replace outdoor unit PCB.
If voltage is normal but sparking noise cannot be heard, replace the ignition electrode.
Caution: If the ignition wires are disconnected, connect them by pushing them in firmly.
2) Check gas valve (GV1).
Measure DC voltage at the connector (CN08) of electromagnetic valve (under heating operation, during com-
bustion).
In case of abnormality 
Replace outdoor unit PCB.
Normal
WHT – WHT  DC 90 – 120 V
*
Use a circuit tester (set to AC range).
*
Use a circuit tester (set to DC range).