York DM 240 ユーザーズマニュアル

ページ / 40
262259-YTG-B-0107
6
Unitary Products Group
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent 
operation at excessive temperatures.
VARIABLE AIR VOLUME (VAV) - A factory-installed 
variable frequency drive (VFD), mounted in the Blower 
Access compartment, is used to control the speed of the 
indoor blower motor in order to maintain a constant static 
pressure in the supply duct. A pressure transducer and 
VAV control board are mounted inside the control box. 
The drive comes completely wired and pre-programmed 
from the factory.
An optional, factory-installed manual bypass switch 
available with factory-installed VFD can be found in the 
Blower Motor Access compartment. The switch can be 
used to either route power to the VFD for modulating 
control of the blower motor, to bypass the drive and oper-
ate the motor at full speed, or to power the drive (and not 
the motor) for diagnostic purposes.
Due to space limitations, VAV is not available with any of 
the factory-installed BAS options described below, but is 
available with ‘BAS-ready’ models. Terminal blocks are 
provided in the control box for field wiring of the cus-
tomer-installed BAS.
A ‘VFD-ready’ option provides the provisions for a cus-
tomer-installed drive. The unit comes with a mounting 
bracket installed in the Blower Access compartment 
which may accommodate other vendor’s drives depend-
ing on their size. In order to utilize the unit’s mounting 
bracket, the maximum recommended drive dimensions 
are as follows:
For 5-hp motor applications........................ 10” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications ........ 13” H x 8” W x 8” D
If the customer-installed drive will not fit in the allotted 
space, then it will have to be mounted within a NEMA-4 
enclosure for outside installation or inside the building on 
a perpendicular wall not subjected to excessive tempera-
ture, vibration, humidity, dust, corrosive gas, explosive 
gas, etc.
A terminal block located in the control box is provided for 
field connection of the VFD controls.
HOT GAS BYPASS - To allow for low cooling load oper-
ation, a direct-acting pressure-modulating bypass control 
valve installed on the system #1 discharge line is used to 
divert high temperature, high pressure refrigerant around 
the TXV in order to maintain a desired minimum evapo-
rator pressure. HGBP is standard on all units with VAV 
and optional with CV units.
FILTER OPTIONS - Standard units are shipped with 2” 
throw-away filters installed. 2” pleated and 4” pleated fil-
ters are offered as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be 
“powered” by the unit with a stepdown transformer or 
you may order the unit with a “non-powered” conve-
nience outlet that can be wired in the field.
DISCONNECT SWITCH - For gas heat units and cooling 
units with electric heat, a HACR breaker sized to the unit 
is provided. For cooling only units, a switch sized to the 
largest electric heat available for the particular unit is 
provided. Factory installed option only.
BAS - Building Automation System Controls (avail-
able on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York® 
Simplicity® INTELLI-Comfort™ control is factory 
installed. It includes a supply air sensor, a return air sen-
sor, and an outside air sensor. There are provisions for a 
field installed dirty filter indicator switch, an air-proving 
switch, an Outside Air Humidity sensor, a Return Air 
Humidity sensor, an Inside IAQ sensor, and an Outside 
Air IAQ sensor. Construction mode operation, 365-day 
real time clock with 7 day programming plus holiday 
scheduling is built-in. Two different modes of demand 
ventilation are achieved through the INTELLI-Comfort™ 
using CO
2
 sensors. It uses an inside CO
2
 sensor to per-
form Demand Ventilation. It can also use an Outside CO
2
 
sensor to perform Differential Demand Ventilation. It 
uses a Patented Comfort Ventilation algorithm to provide 
comfortable ventilation air temperature. The patented 
economizer-loading algorithm will protect the equipment 
when harsh operating conditions exist. Humidity in the 
occupied space or return duct can be monitored and 
controlled via humidity sensors and the on-board con-
nection for hot gas re-heat system. It uses the INTELLI-
Start™ algorithm to maximize energy savings by recov-
ering the building from the Unoccupied Setpoints to the 
Occupied Setpoints just in time for the Occupied Time 
Period to begin. The Simplicity® INTELLI-Comfort™ bal-
ances space temperature, ventilation air temperature, 
CO
2
 and humidity for ultimate comfort.
Simplicity® INTELLI-Comfort™ with ModLINC CON-
TROL - 
The York® Simplicity® INTELLI-Comfort™ with 
ModLINC control is factory installed. It includes all the 
features of the INTELLI-Comfort™ control with an addi-
tional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building 
automation system controller is factory installed. 
Includes supply air sensor, return air sensor, dirty filter 
indicator switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson 
Control YK-UNT-1126 building automation system con-
troller is factory installed. Includes supply air sensor, 
return air sensor, dirty filter indicator switch, and air prov-
ing switch.
CPC BAS CONTROL - The Computer Process Controls 
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes