Honeywell S7999B ユーザーズマニュアル

ページ / 68
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
3
65-0303—05
The software upgrade is automatic after the above steps. The 
OI Display connects to the Honeywell server, which verifies the 
configuration file, erases the old application and downloads the 
new one.
The OI Display may have difficulty finding the new 
configuration file at first. In this case, the procedure 
automatically starts over again until it works.
S7999C Only
Software upgrades for S7999C OI Display (when needed) will 
be provided by Honeywell and are accomplished through the 
MMC port located on the top back of the device.
SPECIFICATIONS
Electrical Ratings:
+12 Vdc input, maximum of 500 mA current drain.
Included Power Supply for S7999B:
Inputs: 85 to 264 Vac, 47 to 63 Hz; 120 to 370 Vdc.
Output: 12 Vdc; 0 to 2.1 A.
Power: 25 W.
Included Power Supply for S7999C:
Inputs: 100 to 240 Vac.
Output: 12 Vdc; 0.42 A.
Power: 25 W.
Operating Temperature:  32°F to 122°F (0°C to 50°C)
Storage/Shipping Temperature: -40°F to 158°F
 (-40°C to 70°C).
Humidity:
85% maximum relative humidity.
Approvals:
FCC Part 15, Class A Digital Device
Underwriter’s Laboratories, Inc. (UL) (cUL) Component 
Recognized (for non-continuous operation): File Number 
MH20613 (MCCZ)
Canada: ICES-003
Dimensions:  See Fig. 1.
Replacement Parts (S7999B)
• 9-pin connector—50020034-001
• Power Supply—Manufactured by MeanWell,
Model S-25-12 (order from manufacturer).
• #6-32 X1-in. screws(4) with nuts (4)
Supplied Parts (S7999C)
• Mounting Plate - see Fig. 9 for dimensions and hole 
locations.
• #6-32 X 1-in. screws (4) with nuts (4)
• Standoffs 5/16-in. dia. X 3/8 in. long (4)
• Power Supply—Manufactured by V-infinity
Model FSC-S5-12U (order from manufacturer).
Fig. 1. OI Display dimensions (S7999C shown) in in. (mm).
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the 
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment 
is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if 
not installed and used in accordance with the instruction manual, may cause harmful interference to radio communica-
tions. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be 
6-21/32
(169)
9-7/16 (240)
7-19/32 (193)
1-33/64 
(39)
M29867A
PANEL HOLE CUTOUT SIZE 7-19/32 (193) WIDE X 5-13/32 (137) HIGH FOR S7999B DISPLAY 7.6 WIDE X 5.4 HIGH..
1
1
5-13/32
(137)
1
8-15/16 (227)
3-1/2
(89)