Honeywell SMV 3000 ユーザーズマニュアル

ページ / 217
1/99
SMV 3000 Transmitter User’s Manual
129
11.4
Diagnostic Messages,  
Continued
Diagnostic Messages,
continued
Table 32
Non-Critical Status Diagnostic Message Table, continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
Possible Cause
What to Do
5-5
Input Mode PV2 (AP)
STATUS  TAG ID.#
INPUT MODE PV2
INPUT MODE PV2
Transmitter is simulating input for
PV2.
Exit Input mode:
SCT – Press “Clear Input Mode”
button on the AP InCal tab.
SFC – Press [
SHIFT
], [
INPUT
], and
[
CLR
] keys.
5-6
Input Mode PV3 (Temp)
STATUS  TAG ID.#
INPUT MODE PV3
INPUT MODE PV3
Transmitter is simulating input for
PV3.
Exit Input mode:
SCT – Press “Clear Input Mode”
button on the TEMP InCal tab.
SFC – Press [
SHIFT
], [
INPUT
], and
[
CLR
] keys.
5-7
Input Mode PV4 (Flow)
STATUS  TAG ID.#
INPUT MODE PV4
INPUT MODE PV4
Transmitter is simulating input for
PV4.
Exit Input mode:
SCT – Press “Clear Input Mode”
button on the FLOW InCal tab.
SFC – Press [
SHIFT
], [
INPUT
], and
[
CLR
] keys.
2-0
Meter Body Sensor Over
Temperature
STATUS  TAG ID.#
  M.B. OVERTEMP
M.B. OVERTEMP
Sensor temperature is too high
(>125 
°
C). Accuracy and life span
may decrease if it remains high.
Take steps to insulate meter body
from temperature source.
2-7
No DAC Temp Comp
Or
DAC Temperature
Compensation data is
corrupt
STATUS  TAG ID.#
NO DAC TEMPCOMP
NO DAC TEMP COMP
Failed DAC.
Replace electronics module.