SMV 3000 Transmitter User’s Manual
83
7.3
Running Output Check,
Continued
Procedure
Table 20
Output Check for SMV Transmitters in DE Mode
Step
Action
1
Connect SCT to SMV and establish communications. (See
Subsection 5.2 for procedure, if necessary.)
Subsection 5.2 for procedure, if necessary.)
2
Be sure any switches that may trip alarms or interlocks associated
with analog loops are secured or turned off.
with analog loops are secured or turned off.
3
Perform Upload of the SMV database to the SCT.
4
Select General tab card and set communication mode to Digital
Enhanced.
Enhanced.
5
Set any of the SMV transmitter PVs to output mode, by selecting the
appropriate tab cards.
appropriate tab cards.
•
DPOutCal, (for PV1)
•
APOutCal, (for PV2)
•
TempOutCal, (for PV3) or
•
FlowOutCal, (for PV4)
6
Enter an output value and then set PV to Output mode.
7
Open the PV Monitor window by selecting PV Monitor from the View
pull down menu. Read the PV outputs.
pull down menu. Read the PV outputs.
Also, check the PV outputs as displayed at the digital receiver.
8
Select appropriate tab card for the PVs that were set to output mode
and clear the output mode.
and clear the output mode.
9
Select Status tab card to verify that all transmitter outputs are in not in
output mode and that there are no new messages.
output mode and that there are no new messages.