T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
3
63-4355—4
Electrical Ratings:
24 Vac, 50/60 Hz.
20 to 30 Vac, 50/60 Hz.
Batteries: No batteries required.
Auxiliary Heat and Emergency Heat Indication: 
Thermostat display indicates when Auxiliary Heat or 
Emergency Heat are activated.
Loss of Power: The thermostat maintains programmed times 
and temperatures for the life of the product. The clock and 
day information is retained for a minimum of two hours.
Light Emitting Diodes (LED):
Two user-defined LED (not available on Q7300H).
Two defined (CHECK and MAINTENANCE) LED on select 
models.
System Current Draw: 6 VA maximum at 30 Vac, 50/60 Hz.
Output Relay Current Draw: See Table 3.
Table 3. Maximum Amps at 30 Vac.
Temperature:
Ratings:
Operating Ambient: 40°F to 110°F (4°C to 43°C).
Shipping: -30°F to +150°F (-34°C to +65°C).
Display Accuracy: ±1°F (±0.5°C).
Setpoint:
Range: 45°F to 95°F (7°C to 35°C).
Deadband: 2°F (1°C).
Default Settings: See Table 4.
Table 4. Default Setpoints.
Remote Sensor Wiring Temperature Offset:
Temperature offset occurs with 500 ft (157m) to 
1000 ft (305m) of 2-wire cable. See Table 5.
Humidity Ratings: 5% to 90% RH, noncondensing.
Clock Accuracy: ±1 minute per month.
Table 5. Temperature Offset.
Minimum Stage Operation Time:
Minimum On (Heat and Cool): factory setting 2 minutes; 
option 0 minutes.
Minimum Off (Cool and Heat Pump): factory setting 
4 minutes; option 0, 1, 3, 5 minutes.
Mounting Means:
T7200: Mounts on a wallplate.
T7300: Mounts on a Q7300 Subbase.
NOTE:
Wallplate and subbase mount horizontally on a wall 
or outlet box with two no. 6 x 32 screws (included).
Accessories:
C7150B1004 Discharge Air Sensor: for checkout use only 
(form 63-2072).
M7415 Damper Actuator (form 63-2100).
ML7984 Valve Actuator (form 95C-10753).
Q7760A Serial LonTalk® Adapter.
R8222 Switching Relay (form 60-2056).
T675A Temperature Control (form 60-2200).
T7022A1010 Remote Temperature Sensor (form 60-0247).
T7047C Remote Temperature Sensor (form 62-3050).
T7047G Remote Temperature Sensor (form 62-3050).
T7147A Remote Temperature Sensor and Override Module 
(form 62-3049).
W859F Packaged Economizer (form 63-2476).
W950A System Supervisor (form 60-2351).
W7459 Economizer Logic Module (form 63-2141).
W6210/W7210 Economizer (form 63-2528).
W6215/W7215 Economizer (form 63-2544).
Approvals:
European Community Mark (CE) Listed.
Q7300H only: L
ON
M
ARK
® Functional Profile No. 8060, 
Thermostat Object (type 09).
MERCURY NOTICE
If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash. Dispose of properly.
Contact your local waste management authority 
for instructions regarding recycling and the proper 
disposal of an old control. If you have questions, 
call Honeywell Customer Response Center at 
1-800-468-1502.
Relay
Running (A)
Inrush (A)
Fan
0.5
2.5
Heat (all stages)
1.5
3.5
Cool (all stages)
1.5
7.5
Auxiliary (Economizer)
1.5
3.5
Control
Occupied
Unoccupied
Heating
70°F (21°C)
55°F (13°C)
Cooling
78°F (26°C)
90°F (32°C)
Temperature Range
18 AWG
20 AWG
22 AWG
50 to 90°F
-0.4°F
-0.7°F
-1.0°F
10 to 32°C
-0.3°C
-0.4°C