T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
60-2485—8
10
Outdoor Disconnect
The National Electrical Code requires the installation of a 
disconnect switch within sight of the outdoor unit of an air 
conditioner or heat pump. The switch is for the safety of any 
technician working on the unit. The technician can assure that 
the unit remains unpowered.
Install and Adjust Stop Brackets
The stop brackets should be installed only if there is a need to 
restrict the adjustable range of the heating and cooling 
temperature setpoint levers. If adjustable lever stops are 
desired, order 4074ECK Envelope Assembly, which contains 
two adjustable lever stop brackets, one brass insert, one 
mounting screw and two locking screws with insulated heads. 
When installed, the stop brackets limit the movement of the 
T874 HEAT and COOL levers.
TO INSTALL:
1. Remove the thermostat cover by pulling the bottom 
edge of the cover upward until it snaps free of the 
mounting slots.
2. Turn to the back of the T874 Thermostat. Locate the 
hole for the brass insert in the plastic base below the 
LED window.
3. Push the brass insert into the hole with finger.
4. Turn to the front of the T874 Thermostat.
5. Place the two stop brackets in position with the tabs in 
the slot between the HEAT and COOL levers. See 
Fig. 9.
Fig. 9. Range limiting and lever locking methods.
6. Insert the mounting screw into the two slots in the stop 
brackets and attach to the brass insert. Tighten the 
screw to pull the brass insert into the back of the ther-
mostat.
7. Loosen the mounting screw enough to free the stop 
brackets for adjustment.
T
External temperature readout, T relay
R1, R2
LO and HI speed fan relays
RS
Cooling contactor
Y
M
Compressor contactor
Table 5. Terminal Designations
a
Standard Terminal 
Designation
Alternate Designations or 
Customer Specials
Typical Connection
a
Other terminal designations can be used that are not listed on this table. Refer to the hookup drawing and internal schematic 
for exact connections.
b
W3 controls the auxiliary heat like W2, and allows adding additional stages of auxiliary heat with outdoor thermostats while 
maintaining the proper second stage anticipation.
HEAT
LEVER
HOLES FOR INSULATED
LOCKING LEVER SCREWS
COOL
LEVER
HOLE WITH
BRASS INSERT
BRACKET
TABS
ADJUSTABLE
LEVER STOP
BRACKETS
BRACKET
SLOTS
MOUNTING 
SCREW
ADJUSTABLE STOPS
ADJUSTABLE LOCKING LEVERS
NONADJUSTABLE STOPS
WITH LOCKING LEVER SCREWS
75
°
F (24
°
C) MAX. HEAT
75
°
F (24
°
C) MIN. COOL
NONADJUSTABLE D.O.D. STOPS
72
°
F (22
°
C) MAX. HEAT
78
°
F (26
°
C) MIN. COOL
M7626