Honeywell T8400C1099 ユーザーズマニュアル

ページ / 8
T8400C1099, T8401C1031 ELECTRONIC THERMOSTATS
69-1484-2
6
NOTE: In installer setup mode only, each press of the 
 key momentarily displays 01. Each press of 
the ▼ key momentarily displays 02. When the 
keys are released, these two-digit codes are no 
longer displayed. 
3. Press the ▲ key. Factory information is displayed. 
A typical example is shown, but information dis-
played varies by model. This information is for fac-
tory use only.
4. Press the ▲ key again to display °C or °F.
5. Press the  ▼ key to change the °C or °F indication.
6. Press the ▲ key to display the heat cycle rate of 1, 
3, 4, 5, 6, 9, or 12. To change the heat cycle rate, 
press the ▼ key to scroll between 1, 3, 4, 5, 6, 9, or 
12. Stop scrolling when the desired rate is dis-
played. See Table 1 for the cycle rate options and 
the corresponding system equipment.
7. Press the ▲ key to display heating/cooling temper-
ature control default..
8. Press the ▼ key again to change heating/cooling 
temperature control to C1 or C3.
C1 = Standard heating/cooling temperature 
control.
C3 = Aggressive heating/cooling temperature 
control (can cause room temperature to 
overshoot the setpoint).
9. Press the ▲ key again. Factory information (varies 
by model) is shown.
Table 1. Heating Cycle Rates.
a
High efficiency furnace.
b
Refer to equipment manufacturer’s instructions.
10. Press the ▲ key to save all changes, exit installer 
setup mode and return to normal operation.
NOTE: After exiting installer setup mode, slide the   
System switch to the desired position and 
change the setpoint to the desired room       
temperature.
CHECKOUT
Heating
1. Slide the SYSTEM switch to Heat and the FAN 
switch to Auto.
2. Press and hold the ▲ key to raise the temperature 
setting several degrees above the room tempera-
ture. After approximately ten seconds, the heating 
equipment should start. In conventional systems, 
the system turns on the fan through the use of a 
time delay relay or through a limit control. When 
using an electric heat thermostat, the fan starts 
immediately.
3. Press the ▼ key to lower the temperature setting 
below the room temperature. Heating equipment 
should stop.
Cooling
CAUTION
Low Temperature Hazard.
Operating at too low of an outdoor 
temperature may cause compressor damage.
Do not operate cooling if outdoor temperature is 
below 50°F (10°C). Refer to manufacturer’s 
recommendations. 
• For compressor protection, during power 
interruption and on initial startup, the T8400 
and T8401 Thermostats go into a five-minute 
delay. During this delay, the cooling icon (a 
snowflake ❄) flashes.
1. Slide the SYSTEM switch to Cool and the FAN 
switch to Auto.
2. Press the ▼  key to lower the temperature setting 
several degrees below the room temperature. After 
approximately five minutes, the cooling equipment 
should start. The fan starts and stops with the cool-
ing equipment.
M14687
M14688
M14689
M14690
M18419A
M18420
System
Cycles Per Hour
Steam, gravity
1
Hydronic heat, condensing gas 
furnace
a
3
Gas or oil forced air
6
Electric heat
9
Special applications
b
4, 5, 12