CM900 Wireless - Programmable Room Thermostat
4.3 Using the Room Thermostat for Specific Applications
The CM927/921 RF room thermostat is a versatile controller that can be used to control many different 
applications. For most typical applications, like wall-hung gas fired combination boiler control or zone 
valve control, no adjustments from the factory settings are required. For other applications, like controlling 
an oil burner, the best system performance can be achieved by modifying selected parameters of the 
room thermostat in the Installer mode. The table below lists the most common settings used for specific 
applications.
4.4 Using the Special Features of the Room Thermostat
Special Feature:
Description:
Enable/Disable
Optimisation 
(Variable Start 
Time)
The thermostat will adjust the start time in the morning/afternoon so the 
desired temperature is reached by the start of the program period. The 
system will restrict the start time to a max of 2 hours.
To enable: Set parameter 8:
OP (category 1) to 1.
Heating or Cooling 
Operation
This product can be used for heating or cooling applications. If you select 
cooling mode the control algorithm and factory default program will be 
modified. You can independently modify the heating and cooling profile.
To enable: Set parameter 4:
HC (category 2) to 1.
Summer/Winter 
Auto time change
This feature moves time automatically on the last Sunday of March and 
the last Sunday of October. The feature is factory enabled.
To enable: Set parameter 3:
tC (category 1) to 1.
Temperature Offset
If the thermostat is located in a particularly hot/cold location for reliable 
signal transmission reasons then the measured/displayed temperature 
can be adjusted by +/- 3°C. This is useful if the homeowner wants the 
reading to match another appliance temperature display.
Set parameter 12:tO 
(category 1) to the required 
offset value.
Upper/Lower 
Temperature Limit
The normal upper temperature limit of 35°C can be reduced to 21°C 
to save the homeowner energy. The normal lower limit of 5°C can be 
increased up to 21°C to protect inhabitants from cold.
Set parameter 6:uL (category 
1) to the desired upper limit.
Set parameter 7:LL (category 
1) to the desired lower limit.
Specific Application:
Setting:
What to change:
Cycle/ 
Hour
Minimum ON 
Time
Note:
 All parameters listed below belong to category 2 
- System Parameters (see Installer Parameters Table)
HEATING
Gas Boiler (<30kW)
6
1
No changes required
Oil Boiler
3
4
Set 1:Ot parameter to 4 
Set 2:Cr parameter to 3
Thermal Actuator
12
1
Set 2:Cr parameter to 12
Zone Valve
6
1
No changes required
AIR- 
CONDITIONING
To enable switching between cooling and heating 
modes adjust parameter 4:HC in category 2 (0 =
disabled, 1 = enabled). Now you can switch between
these modes by pressing the     and   buttons 
together for 5 seconds in any of the product operating 
modes (AUTOMAN or OFF). Explain to the end user 
how to switch between these modes using the     and 
 buttons and ensure the cooling program is modified 
as required.
Heat Pump / Air-
Conditioner
3
4
Set 1:Ot parameter to 4 
Set 2:Cr parameter to 3
Fan Coil
6
1
No changes required