Honeywell T7350 ユーザーズマニュアル

ページ / 40
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
13
63-2605—5
No options lockout special keypresses. See 
the Special Functions section for details.
4. Once the proper option is chosen, exit Installer Setup by 
pressing Run Schedule.
5. The display prompts SAV CFG (save configuration). If 
you want to save it, use the up S or down T key to 
change NO to YES before pressing Run Schedule 
again.
Configuration
CAUTION
Possible Equipment Damage.
Fan must be running when system is operating.
Heat pump and electric heat systems must be 
configured correctly to prevent equipment damage 
caused by the system running without the fan.
Limited configuration can be done with the keypad. In order to 
determine the proper codes to use for the Configuration 
Variables (CnfgID), a PDA is required:
1. Open the PDA Config Tool Application.
2. Select the desired configuration.
3. On the summary screen, tap CnfgID.
4. The PDA determines the proper CnfgID.
5. Make note of the values.
6. Press both Copy and Run Schedule.
7. Tap 
 until C1 appears on the right end of the display.
8. Adjust each variable to match the PDA indication:
a. Hold down the up S or down T key to adjust the 
value quickly.
b. Tap the up S or down T key for fine control.
9. Press 
 to switch to another variable.
10. Return to step and repeat the process until all digits 
are set properly.
11. To exit the Installer Setup, press Run Schedule.
12. The display prompts SAV CFG (save configuration).
a. If you want to save the new configuration, use the 
up S or down T key to change NO to YES before 
pressing Run Schedule.
b. If you want the configuration to remain as it was 
before starting this change, ensure the display 
indicates SAV CFG NO and press Run Schedule.
IMPORTANT
1. Review the settings to confirm that they are correct 
for the system.
2. Press Run Schedule to exit the Installer Setup.
3. The thermostat prompts you to save configuration 
changes. Default is NO.
4. Be sure to set the current day and time immediately.
Special Functions
Restore Factory Configuration (Run/Clear)
IMPORTANT
This operation erases the current configuration and 
restores the factory defaults for all configuration, 
parameters, setpoints and schedules. To regain the 
old requires device reconfiguration.
1. Press both Run Schedule and Clear Start Time.
2. The display gives the option to restore the FAC CFG.
a. To restore the factory defaults, press up S or 
down T until the display indicates YES.
b. To cancel this option, ensure display indicates NO.
3. Press Run Schedule.
Get Factory Schedule (Info/Clear)
Performing this operation reverts the schedules to the factory 
defaults:
1. Press both Info and Clear Start Time.
2. The display gives the option to restore the FAC SCH.
a. To restore the factory schedule, press up S or 
down T until the display indicates YES.
b. To cancel this option, ensure display indicates NO.
3. Press Run Schedule.
Test Mode (Occupied/Not Occupied/Schedule Day)
CAUTION
Possible Equipment Damage.
Equipment damage can result if compressor is 
cycled too quickly.
The minimum off time for compressors is bypassed 
during Test Mode. Equipment damage can occur if the 
compressor is cycled too quickly.
Use the Test Mode to check the thermostat configurations and 
operation. To start the system test:
1. Press Schedule Day, Occupied and Not Occupied 
simultaneously.
2. The display gives the option to TEST.
a. To enter test mode, press up S or down T until the 
display indicates IN TEST.
b. To cancel this option, ensure the display indicates 
NO TEST.
3. Press Run Schedule.
NOTES:
To verify whether or not the system test is still 
active, repeat the above process.
The system test times out after ten minutes with 
no key pressed.
Save User Schedule (Info/Copy)
Performing this operation saves the current schedule 
(including holidays) to memory, overwriting the old saved 
schedule:
1. Press both Info and Copy.
2. The display gives the option to SAV SHD.
a. To save the current schedule, press up S or down 
T until the display indicates YES.
b. To cancel this option, ensure display indicates NO.
3. Press Run Schedule.
Get User Schedule (Info/Run)
Getting the user schedule restores the schedule (including 
holidays) from saved memory, overwriting the schedule 
currently in use:
1. Press both Run Schedule and Info.
2. The display gives the option to GET SHD.
a. To retrieve the saved schedule, press up S or 
down T until the display indicates YES.
b. To cancel this option, ensure display indicates NO.
3. Press Run Schedule.