Honeywell 95-7769-01 ユーザーズマニュアル

ページ / 176
WEBVISION™
95-7769—01
140
Occupied Heat (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0
Standby Heat (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0
Unoccupied Heat (Setpoint)
X
 Units=ºC
 Precision=2
 Min=10.0
 Max=35.0
Current State
X
 ocOccupied
 ocUnoccupied
 ocBypass
 ocStandby
 ocNul
Next State
X
 ocOccupied
 ocUnoccupied
 ocBypass
 ocStandby
 ocNul
Time To Next State
X
 Units=min
 Precision=0
 Min=0.0
 Max=65535.0
DLC Shed
X
 dlNoDlcShed
 dlMinDlcShed
Air Flow Loss
X
 false or true
Communication Failed
X
 false or true
Dirty Filter
X
 false or true
Drip Pan Full
X
 false or true
Freeze State
X
 false or true
Frost Protect
X
 false or true
Indoor Air Quality Override
X
 false or true
Invalid Setpoint
X
 false or true
Low Limit Economizer Close
X
 false or true
Node Disabled
X
 false or true
Outside Air Quality
X
 false or true
Sensor Failed
X
 false or true
Table 85. UV Application of Points. (Continued)
Point Name
Graphics Alarms Trends
Commandable
Internal Use
Valid Values