WEBVISION™
45
95-7769—01
7. Choose the number of cooling stages (1-4) or the type 
(PWM or Floating) from the Cooling list. 
8. Select the type of economizer from the Economizer list. 
a. If the heating, cooling, or economizer is configured 
as PWM, the Period, Zero Scale, and Full Scale 
settings must be configured.
b. If the heating, the cooling, or the economizer is 
configured as Floating, the Motor speed settings 
must be configured. 
9. Configure the Optional points. Refer to Table 16 on 
page 45 for possible values.
10. Click Commit to save the settings or Reset to revert to 
the last saved settings. 
11. Click Next to display the Input Configuration page. 
CVAHU Controller Outputs
Table 16 lists the CVAHU Outputs for each controller model.
NOTE: The optional points Free1AO, Free2AO, 
Free1AORev, Free2AORev are available in the 
W7750C Model of CVAHU only. These enumerations 
must be selected to use terminals 6,7 and 8 of 
W7750C model. These outputs can be driven by 
XL15A or XL15C, but since Free1 and Free2 are 
digital in nature, XL15A and XL15C can only 
command these points to ON or OFF. Hence, these 
points can be driven only by digital outputs of Xl15A/
Xl15C loops.
CVAHU Outputs fields
Table 17 lists the CVAHU Outputs fields.
Table 16. CVAHU Outputs for each Model.
Output
W7750A
W7750B
W7750C
Heating
1 to 4 stages
1 to 4 stages, HeatPWM or 
HeatingFloating
1 to 4 stages, HeatPWM, 
HeatPWMRev, HeatAO, 
HeatAORev, or HeatingFloating.
Cooling
1 to 4 stages
1 to 4 stages, CoolPWM or 
CoolingFloating
1 to 4 stages, CoolPWM, 
CoolPWMRev, CoolAO, 
CoolAORev, or CoolingFloating.
Economizer
EconNone or EconFloating
EconNone, EconPWM, or 
EconFloating
EconNone, EconPWM, 
EconPWMRev, EconAO, 
EconAORev or EconFloating.
Optional Points OccStatus, AuxEcon, Free1, Free2, 
Free1PulseOn, Free1PulseOff.
Maximum of one optional point.
OccStatus, AuxEcon, Free1, Free2, 
Free1PulseOn, Free1PulseOff.
Maximum of three optional points.
OccStatus, AuxEcon, Free1, 
Free1Rev, Free2, Free2Rev 
Free1PulseOn, Free1PulseOff, 
Free1AO, Free1AORev, Free2AO, 
Free2AORev.
No optional points available.
Table 17.  CVAHU Outputs Fields.
Name
Definition
Controller Type
Select one of the following model types: 
• W7750A 
• W7750B 
• W7750C 
The wizard does not allow commissioning 
if incorrect Model Type is selected
Power Frequency Select one of the following options:
• 50 Hz 
• 60 Hz 
Equipment Type
Select one of the following options:
• Conventional 
• HeatPump 
Heating
Refer to table above for selecting Heating 
options:
• If you select Floating, enter the Motor 
Speed settings.
• If you select PWM, enter the PWM 
settings.
Cooling
Refer to the table above for selecting 
Cooling settings:
• If you select Floating, enter the Motor 
Speed settings.
• If you select PWM, enter the PWM 
settings.
Economizer
Refer to the table above for selecting 
Economizer options:
• If you select Floating, enter the Motor 
Speed settings.
• If you select PWM, enter the PWM 
settings.
Table 17.  CVAHU Outputs Fields. (Continued)
Name
Definition