Honeywell 96D ユーザーズマニュアル

ページ / 80
14  
96d User Manual 
M-511401
Honeywell 
8/10
Introduction
Power Connections
Power Connections
The 96D requires a power range of 17-27 Vac, 50/60 Hz (8.64 VA), 18-
36 Vdc, 350 mA @24 Vdc (8.4 VA).  Polarization is not important in 
either AC or DC mode.  The system must be grounded on the 
transformer and a dedicated circuit breaker must be used.
Communication Connections
Communication cables must be grounded using the shield terminal, 
using twisted and shielded pair Belden 2-24 AWG #9841 cable (or 
equivalent).
The network cabling can extend up to a limit of 2000 feet (609 m) per 
channel.
The length of a T-tap can reach 65 feet (20 m), up to a maximum of 130 
feet (40 m) for all T-taps.
All wireless devices associated to the controller will automatically be 
detected and communicate with the controller using wireless 
communication protocols.
Settings for Specific Transmitters
Honeywell Sensepoint XCD Transmitters must be configured for 9600 
baud, no parity, and a unique address. Honeywell XNX Universal 
Transmitters must be configured for 9600 baud and a unique address.  
Information on configuring each transmitter is in the associated 
technical manual.