Mitsubishi Electronics QJ71DN91 ユーザーズマニュアル

ページ / 150
9 - 2                                                                                                                                                       9 - 2
MELSEC-Q
9   TROUBLESHOOTING
 9
9.1 Items to Check When an Error Occurs
This section explains the items to check when an error occurs and its troubleshooting
procedure:
9.1.1 Checking the LEDs
Is the NS LED lit in green 
or flashing in green?
Occurrence of an error
Is the mode switch set 
between 0 and 8?
No
Reset by setting the mode switch between 
0 and 8.
Yes
Is the MS LED lit in green?
(The NS LED is off.) 
Turn ON the module power.
Is the NS LED lit?
Turn ON the network power (24V).
Is the NS LED lit in red?
Check the following:
•   Is the node number between 0 and 63?
•   Does a duplicate node number exist within 
    the network?
•   Is the communication speed uniform in the 
    entire network?
•   Is a terminal resistor installed at both ends of 
    the trunk line?
Check the error code.
If all of the above check items are normal, check 
the entire network status such as noise and installation.
Is the ERR. LED lit?
Turn ON the "I/O communication request" (Y11).
Is the NS LED flashing in red?
An I/O communication error has 
occurred with one or more slave stations. 
Check the error code with 1B1
H
master function for error information 
function" and 601
H
, "slave function for error 
information" of the buffer memory, 
and take an appropriate action.
A parameter error has occurred. 
Check the error code with 1B1
H
"master function for error information" 
and 601
H
, "slave function for error 
information" of the buffer memory, 
and take an appropriate action.
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
No