9.5 Troubleshooting for monitoring
 
9.5 Troubleshooting for monitoring
The following describes the corrective action when the GOT monitoring screen is blank.
*1  Refer to GOT-A900 Series Operating Manual (Extended _ Option Functions Manual), for utility menu.
*2  Refer to the following manual for details of the forced screen save signal.
 
When GT Designer is used:Help function of GT Designer
 
When GT Designer2 is used:GT Designer2 Version Reference Manual
The GOT screen is blank
The GOT Power LED is off.
The screen will come back on 
by touching the display section.
If the screen will come back, this means the 
screensaver is set.
The backlight has 
reached its maximum life span.
Power on the GOT.
This function can be set within the GOT utility 
menu.    1
System information function 
(system signal 1) is set.
Check the bit status.
The bit of "Forces Screen Saver Enable Signal" 
for GOT may be on.
If bit is on, turn it off.     2
(Compare the backlight life span and 
the operating time.)
Possible cause is GOT hardware fault.
Consult your sales representative.
NO
YES
Replace the backlight.
NO
NO
NO
YES
YES
YES