4. OPERATION 
 
4.4.5 Stopper type home position return 
In stopper type home position return, a machine part is pressed against a stopper or the like by jog 
operation, manual pulse generator operation or the like to make a home position return and that position 
is defined as a home position. 
 
(1) Signals, parameters 
Set the input signals and parameters as follows. 
Item Device/Parameter 
used 
Description 
Automatic/manual selection (MD0) 
Short MD0-SG (ON). 
Point table No. selection 1 (DI0) 
Open DI0-SG (OFF). 
Manual home position return 
mode selection 
Point table No. selection 2 (DI1) 
Open DI1-SG (OFF). 
Stopper type home position 
return 
Parameter No.8 
3 : Stopper type home position return is 
selected. 
Home position return 
direction 
Parameter No.8 
Refer to section 4.4.1 (2) and choose the home 
position return direction. 
Home position return speed 
Parameter No.9 
Set the speed till contact with the stopper. 
Stopper time 
Parameter No.44 
Time from when the part makes contact with 
the stopper to when home position return data is 
obtained to output home position return 
completion (ZP) 
Stopper type home position 
return torque limit 
Parameter No.45 
Set the servo motor torque limit value for 
execution of stopper type home position return. 
Home position return 
acceleration time constant 
Point table No.1 
Use the acceleration time constant of point table 
No.1. 
Home position return 
position data 
Parameter No.42 
Use to set the current position on completion of 
home position return.