13. CHARACTERISTICS 
 
13. CHARACTERISTICS 
13.1 Overload protection characteristics 
An electronic thermal relay is built in the servo amplifier to protect the servo motor and servo amplifier 
from overloads. Overload 1 alarm (AL.50) occurs if overload operation performed is above the electronic 
thermal relay protection curve shown in any of Figs 13.1. Overload 2 alarm (AL.51) occurs if the 
maximum current flew continuously for several seconds due to machine collision, etc. Use the equipment 
on the left-hand side area of the continuous or broken line in the graph. 
In a machine like the one for vertical lift application where unbalanced torque will be produced, it is 
recommended to use the machine so that the unbalanced torque is 70% or less of the rated torque. 
 
1000
100
10
1
0.1
0
50
150
200
250
300
(Note) Load ratio [%]
Ope
rat
ion t
im
e[
s]
During rotation
During stop
100
 
a. MR-J2S-10CP to MR-J2S-100CP 
1000
100
10
1
0.1
0
50
100
150
200
250
300
(Note) Load ratio [%]
Op
er
at
io
n ti
me
 [s]
During rotation
During stop
 
b. MR-J2S-200CP to MR-J2S-350CP 
0
50
100
150
200
250
300
1
10
100
1000
10000
(Note) Load ratio [%]
Operat
io
n
 ti
m
e[
s]
During rotation
During servo lock
 
c. MR-J2S-500CP MR-J2S-700CP 
 
Note. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor 
stop status (servo lock status) or in a 30r/min or less low-speed operation status, the servo amplifier may fail even when the 
electronic thermal relay protection is not activated. 
Fig 13.1 Electronic thermal relay protection characteristics