11. TROUBLESHOOTING 
 
11.4 When alarm or warning has occurred 
POINT 
 
Configure up a circuit which will detect the trouble (ALM) signal and turn off the 
servo-on (RYn0) at occurrence of an alarm. 
 
11.4.1 Alarms and warning list 
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or warning 
has occurred, refer to section 11.4.2 or 11.4.3 and take the appropriate action. When an alarm occurs, ALM 
turns off. 
After its cause has been removed, the alarm can be deactivated in any of the methods marked   in the alarm 
deactivation column. 
 
Alarm deactivation 
  Display
Name 
A90 
Home positioning incomplete 
warning 
A92 
Open battery cable warning 
A96 Home 
position 
setting 
error 
  Display Name  Power 
OFF ON
(Note3) 
MR 
Configurator
parameter 
unit 
(Note2)
Alarm 
reset 
(RES) 
A98 
Software limit warning 
A10 Undervoltage 
 
 
 
A99 
Stroke limit warning 
A12 
Memory error 1 (RAM) 
 
 
 
A9D  CC-Link warning 1 
A13 Clock 
error 
 
 
 
A9E  CC-Link warning 2 
Memory error 2  
A9F 
Battery warning 
A15 
(EEP-ROM) 
 
 
 
AE0 Excessive 
regeneration 
warning 
Encoder error 1 
 
AE1  Overload warning 1 
A16 
(At power on) 
 
 
 
AE3  Absolute position counter warning
A17 Board 
error 
     AE6 
Servo 
emergency 
stop 
warning 
Memory error 3  
A19 
(Flash-ROM) 
 
 
 
AE8 
Cooling fan speed reduction 
warning 
A1A Motor 
combination 
error 
 
 
 
AE9  Main circuit off warning 
A20 
Encoder error 2 
 
 
 
AEC  Overload warning 2 
A24 
Main circuit error 
 
 
 
Warni
ngs
 
AED  Output watt excess warning 
A25 Absolute 
position 
erase 
 
 
 
   
 
 
(Note 1) 
(Note 1) 
(Note 1)    
 
 
A30 Regenerative 
error 
 
 
 
   
 
 
A31 Overspeed 
 
 
 
   
 
 
A32 Overcurrent 
 
 
 
   
 
 
A33 Overvoltage 
 
 
 
   
 
 
A35 
Command pulse frequency alarm 
 
 
 
   
 
 
A37 Parameter 
error 
 
 
 
   
 
 
A45 
Main circuit device overheat 
(Note 1) 
 
(Note 1) 
 
(Note 1)
 
   
 
 
A46 Servo 
motor 
overheat 
(Note 1) 
 
(Note 1) 
 
(Note 1)
 
   
 
 
A47 
Cooling fan alarm 
 
 
 
   
 
 
A50 Overload 
(Note 1) 
 
(Note 1) 
 
(Note 1)
 
   
 
 
A51 Overload 
(Note 1) 
 
(Note 1) 
 
(Note 1)
 
   
 
 
Ala
rm
A52 Error 
excessive 
 
 
 
   
 
 
 A61 
Operation 
alarm 
 
 
 
   
 
 
 
A8A 
Serial communication time-out 
 
 
 
   
 
 
 A8D 
CC-Link 
alarm 
 
 
 
   
 
 
 A8E 
Serial 
communication 
error 
 
 
 
   
 
 
 888 
Watchdog 
 
 
 
   
 
 
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence. 
2. Turns on RY(n+1)A or RY(n+3)A. 
3. Clicking the "Alarm reset" button on the "Alarm display" screen of MR Configurator allows an alarm to be deactivated. 
Pressing the "STOP RESET" key of the parameter unit allows an alarm to be deactivated.