Install Management Terminal and Activate System 
Page 3-18
Set System Maintenance Parameters 
3
Set System Maintenance Parameters
If the system does not contain a TN778 Packet Control circuit pack, skip this 
section and proceed to 
1. Verify the terminal screen displays: 
Command:
2. Type change system-parameters maintenance
 
and press
 Enter
. Verify 
the screen displayed is similar to 
Screen 3-5
. The screen shows default 
values and the cursor is positioned on 
Product Identification:
 line.
Screen 3-5.
Typical System-Parameters Maintenance Screen
!
CAUTION:
To prevent unnecessary trouble tickets, do not enable the system 
alarms (Alarm Origination feature) until all installation and 
administration procedures are completed.
3. Move the cursor by pressing 
Tab
 
to move down the screen from field to 
field and enter 
y
 in the
 Packet Bus Activated?
 field to indicate a 
TN778 circuit pack is installed. This is the only field needing change on 
this screen to turn the red LEDs off.
4. Press 
Enter
 when the information is correct.