Install and Connect Cabinets 
Page 1-8
Connect AC Power and Ground 
1
!
CAUTION:
The equipment room AC power and ground wiring must be performed by a 
qualified electrician. Refer to DEFINITY Enterprise Communications Server 
Release 6 System Description Pocket Reference, for site requirement 
information.
!
CAUTION:
The power circuit must be dedicated to the system and must not be shared 
with other equipment and must not be controlled by a wall switch. The AC 
receptacle should not be located under the MDF.
!
CAUTION:
System grounding must comply with the general rules for grounding 
contained in Article 250 of the National Electrical Code (NEC), National Fire 
Protection Agency (NFPA) 70, or the applicable electric code in the country 
containing the equipment. For more information, refer to 
.
Connect Ground to AC-Powered System
(J58890CE)
Grounding is relatively simple for an AC-powered system. Basically, the cabinets 
connect to the single-point ground terminal block located at either the AC load 
center or to a separate single-point ground block wired to the AC load center (or 
optional AC protector cabinet). 
The approved ground wire must be a green (or green with yellow stripe), 6 
AWG (#40) (16 mm
2
), copper, stranded wire.
Bond all approved grounds at the single-point ground to form a single 
grounding electrode system.
AC Load Center is 50 Feet (15.2 m) or Less from 
Cabinet
1. At the bottom rear of the PPN cabinet, connect a 6 AWG (#40) (16 mm
2
CABINET GROUND wire to the cabinet ground terminal block. See 
2. Route the CABINET GROUND wire to the single-point ground block at the 
AC load center and connect.
3. At the bottom rear of the first EPN cabinet (if provided), connect a 6 AWG 
(#40) (16 mm
2
) CABINET GROUND wire to the cabinet ground terminal 
block.
4. Route the CABINET GROUND wire to the single-point ground block at the 
AC load center and connect.