DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Connecting Fiber Optic Cables 
Page A-8
Optical Cross-Connect Hardware 
A
Single-Mode Fiber Link (with Attenuators)
Figure A-2.
Typical Single-Mode Connection with Attenuator
1. Connect a 2-foot (0.6 m) patchcord to the TX connector on the local 300A 
transceiver. See 
Figure A-2
.
2. Connect the patchcord to the required attenuator. The attenuator must be 
installed in series with the strand of fiber connecting to the TX connector.
3. Repeat for the TX connector at the opposite end of the fiber link (remote 
EPN). A different value attenuator may be required, depending on the 
amount of fiber loss back to the local system.
NOTE:
If the fiber link is duplicated, route the fiber via a separate 
geographical path,  if possible.  This  way, if  the  standard fiber link is 
damaged, the duplicated fiber remains in service.
Figure Notes
1. 300A Lightwave Transceiver
2. 2-Foot (0.6 m) Patchcord
3. In-Line Attenuator
4. Fiber Plant
5. TX Connector
6. RX Connector
7. Lightguide Interconnect Unit
8. Fiber Optic Cable