Install Telecommunications Cabling 
Page 2-20
Cable Installation 
2
Route the cable from the cabinet to the wall. Place the cable beside 1 of 
the rows of columns in the cable slack manager.
NOTE:
Retainers mounted on the columns keep the cable from protruding 
above the top of the base of the cable slack manager.
Determine the length of the cable required to reach from the cable slack 
manager to the assigned connecting/terminal block.
The cable must be supported on the wall using “D” rings.
Cable slack is stored by coiling the cable around the columns in the cable 
slack manager. The first run should always go across the full length of the 
5 columns in the cable slack manager.
Connect the cable to the assigned connecting/terminal block.
Avoid placing copper cables where they may bend or strain fiber optic 
cables.
Install Control Carrier Outputs Cable
A connector on the rear of the Control Carrier is labeled AUX. A 25-pair cable 
connects the AUX connector to a 110-type terminal block in the yellow field of 
the trunk/auxiliary field. The AUX connector outputs include the following:
Alarm monitoring for the processor interface
7 DC power (-48 VDC) sources for emergency transfer units
3 DC power (-48 VDC) sources for remotely powering a total of 3 attendant 
consoles or executive voice terminal adjuncts
The remote maintenance internal modem connection location
Access to a relay contact is available to actuate a light, bell, or similar type 
customer-supplied device. The relay can be administered to make contact 
when a major, minor, or warning alarm condition occurs in the system
Label Control Carrier Cable 
Place the appropriate AUX connector label on the assigned 110-type terminal 
block row. On the control carrier cable, place a yellow auxiliary label on the 
connectors at each end of the cable. Write “AUX” on each label.