8
 - 13
8.11 Action and Handling of Errors
8.11.2 Warning code list
8
TROUBLESHOOTING
8.11.2
Warning code list
This section describes the descriptions and corrective actions for the warnings detected by 
the QD64D2.
POINT
 • When another warning occurs during warning occurrence, the warning 
code is overwritten as the latest one.
 • After fixing the cause of the warning, reset the warning by the error reset 
command (Y0D). If the cause of the warning is not fixed, the warning is 
detected again.
Table 8.20 Warning code list
Warning 
code
Description
Action
Operation at warning
Warning channel
Other channels
0
(Normal)
----
----
----
3m
[Coincidence output No.m test output not possible]
Turn OFF the all signals listed 
on the left. 
The coincidence 
output test cannot 
be started. 
(The warning does 
not affect the other 
coincidence output 
number.)
The warning 
does not affect 
other channels.
The coincidence output No.m test command (Y0B 
and Y0C) is turned ON while one of the following is 
ON. 
•Count enable command (Y06)
•Continuous comparison No.1 execution command 
(Y09)
•During continuous comparison No.1 execution (X09)
•Continuous comparison No.2 execution command 
(Y0A)
•During continuous comparison No.2 execution (X0A) 
"m" indicates the continuous comparison number 
where the warning occurred.