Mitsubishi Electronics FR-E720-0.1KSC to 15KSC ユーザーズマニュアル

ページ / 60
39
Reset method of protective function
8 TROUBLESHOOTING
When a fault occurs in the inverter, the inverter trips and the PU display automatically changes to one of the following fault or
alarm indications.
If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales
representative.
Retention of fault output signal .. When the magnetic contactor (MC) provided on the input side of the inverter is opened when
a fault occurs, the inverter's control power will be lost and the fault output will not be held.
Fault or alarm indication...........When a fault or alarm occurs, the operation panel display automatically switches to the fault
or alarm indication.
Resetting method.....................When a fault occurs, the inverter output is kept stopped. Unless reset, therefore, the inverter
cannot restart. (Refer to page 39)
When any fault occurs, take the appropriate corrective action, then reset the inverter, and resume operation.
Not doing so may lead to the inverter fault and damage.
Inverter fault or alarm indications are roughly categorized as below.
(1) Error message
A message regarding operational fault and setting fault by the operation panel and parameter unit (FR-PU04 /FR-PU07)
is displayed. The inverter does not trip.
(2) Warning
The inverter does not trip even when a warning is displayed. However, failure to take appropriate measures will lead to a fault.
(3) Alarm
The inverter does not trip. You can also output an alarm signal by making parameter setting.
(4) Fault
When a fault occurs, the inverter trips and a fault signal is output.
8.1 Reset method of protective function
The inverter can be reset by performing any of the following operations. Note that the internal thermal integrated value of the
electronic thermal relay function and the number of retries are cleared (erased) by resetting the inverter.
Inverter recovers about 1s after the reset is released.
REMARKS
For the details of fault displays and other malfunctions, also 
 refer to the Instruction Manual (Applied).
Past eight faults can be displayed using the setting dial. (Refer to page 3 for the operation.)
Operation 1:  ...... Using the operation panel, press 
  to reset the inverter.
(This may only be performed when a fault occurs (Refer to page 40 for fault.))
Operation 2: . ..... Turn ON the reset signal (RES) for more than 0.1s. (If the RES signal is kept
ON, "Err." appears (flickers) to indicate that the inverter is in a reset status.)
Operation 3: ....... Switch power OFF once. After the indicator of the operation panel turns OFF,
switch it ON again.
REMARKS
Use the operation 1 or 2 to reset when using the 24V external power supply. (Inverter with FR-E7DS mounted.)
NOTE
OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting inverter fault with the
start signal ON restarts the motor suddenly.
SD
Inverter
RES
ON
OFF