Control method
Soft-PWM control, high carrier frequency PWM control (selectable among V/F control, Advanced magnetic flux vector 
control, Real sensorless vector control), Optimum excitation control, vector control
, and PM sensorless vector control
Output frequency range
0.2 to 590 Hz (The upper-limit frequency is 400 Hz under Advanced magnetic flux vector control, Real sensorless vector 
control, vector control
, and PM sensorless vector control.)
Frequency 
setting
resolution
Analog input
0.015 Hz/60 Hz (terminal 2, 4: 0 to 10 V/12 bits)
0.03 Hz/60 Hz (0 to 5 V/11 bits or 0 to 20 mA/approx. 11 bits for terminals 2 and 4, 0 to 
10 V/12 bits for terminal 1)
0.06 Hz/60 Hz (0 to 
5 V/11 bits for terminal 1)
Digital input
0.01 Hz
Frequency 
accuracy
Analog input
Within 
0.2% of the max. output frequency (25°C 10°C)
Digital input
Within 0.01% of the set output frequency
Voltage/frequency 
characteristics
Base frequency can be set from 0 to 590 Hz. Constant-torque/variable-torque pattern or adjustable 5 points V/F can be 
selected.
Starting torque
SLD rating: 120% 0.3 Hz, LD rating: 150% 0.3 Hz, ND rating: 200%
 0.3 Hz, HD rating: 250%
 0.3 Hz
(under Real sensorless vector control or vector control
Torque boost
Manual torque boost
Acceleration/deceleration 
time setting
0 to 3600 s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode, 
backlash countermeasures acceleration/deceleration can be selected.
DC injection brake 
(induction motor)
Operation frequency (0 to 120 Hz), operation time (0 to 10 s), operation voltage (0 to 30%) variable
Stall prevention operation 
level
Activation range of stall prevention operation (SLD rating: 0 to 120%, LD rating: 0 to 150%, ND rating: 0 to 220%, HD 
rating: 0 to 280%). Whether to use the stall prevention or not can be selected. (V/F control, Advanced magnetic flux vector 
control)
Torque limit level
Torque limit value can be set (0 to 400% variable). (Real sensorless vector control, vector control
, PM sensorless vector 
control)
Op
er
ati
o
n
 s
p
eci
fi
cati
o
n
s
Frequency 
setting
signal
Analog input
Terminals 2 and 4: 0 to 10 V, 0 to 5 V, 4 to 20 mA (0 to 20 mA) are available.
Terminal 1: -10 to +10 V, -5 to 5 V are available.
Digital input
Input using the setting dial of the operation panel or parameter unit
Four-digit BCD or 16-bit binary (when used with option FR-A8AX)
Start signal
Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected.
Input signals (twelve 
terminals)
Low-speed operation command, Middle-speed operation command, High-speed operation command, Second function 
selection, Terminal 4 input selection, Jog operation selection, Selection of automatic restart after instantaneous power 
failure, flying start, Output stop, Start self-holding selection, Forward rotation command, Reverse rotation command, 
Inverter reset
The input signal can be changed using Pr.178 to Pr.189 (input terminal function selection).
Pulse train input
100 kpps
Operational functions
Maximum and minimum frequency settings, multi-speed operation, acceleration/deceleration pattern, thermal protection, 
DC injection brake, starting frequency, JOG operation, output stop (MRS), stall prevention, regeneration avoidance, 
increased magnetic excitation deceleration, frequency jump, rotation display, automatic restart after instantaneous power 
failure, electronic bypass sequence, remote setting, automatic acceleration/deceleration, intelligent mode, retry function, 
carrier frequency selection, fast-response current limit, forward/reverse rotation prevention, operation mode selection, slip 
compensation, droop control, load torque high-speed frequency control, speed smoothing control, traverse, auto tuning, 
applied motor selection, gain tuning, RS-485 communication, PID control, PID pre-charge function, easy dancer control, 
cooling fan operation selection, stop selection (deceleration stop/coasting), stop-on-contact control, PLC function, life 
diagnosis, maintenance timer, current average monitor, multiple rating, orientation control
, speed control, torque control, 
position control, pre-excitation, torque limit, test run, 24 V power supply input for control circuit, safety stop function, 
vibration control
Output signal
Open collector output (five 
terminals)
Relay output (two 
terminals)
Inverter running, Up to frequency, Overload warning, Output frequency detection, Fault
The output signal can be changed using Pr.190 to Pr.196 (output terminal function selection).
Fault codes of the inverter can be output (4 bits) from the open collector.
Pulse train output
50 kpps
Indi
c
a
ti
o
n
For meter
Pulse train 
output (FM 
type)
Max. 2.4 kHz: one terminal (output frequency)
The monitored item can be changed using Pr.54 FM/CA terminal function selection.
Current 
output
(CA type)
Max. 20 mADC: one terminal (output current)
The monitored item can be changed using Pr.54 FM/CA terminal function selection.
Voltage 
output
Max. 10 VDC: one terminal (output voltage)
The monitored item can be changed using Pr.158 AM terminal function selection.
Operation 
panel
(FR-DU08)
Operating 
status
Output frequency, output current, output voltage, frequency setting value
The monitored item can be changed using Pr.52 Operation panel main monitor selection.
Fault record
Fault record is displayed when a fault occurs. Past 8 fault records and the conditions immediately before the fault (output 
voltage/current/frequency/cumulative energization time/year/month/date/time) are saved.