Power supply harmonics
68
3.2.2
Harmonic Suppression Guidelines in Japan
Harmonic currents flow from the inverter to a power receiving point via a power transformer. The Harmonic Suppression 
Guidelines was established to protect other consumers from these outgoing harmonic currents.
The three-phase 200 V input specifications 3.7 kW or lower were previously covered by "the Harmonic Suppression Guidelines for 
Household Appliances and General-purpose Products" and other models were covered by "the Harmonic Suppression Guidelines for 
Consumers Who Receive High Voltage or Special High Voltage". However, the transistorized inverter has been excluded from the target 
products covered by "the Harmonic Suppression Guidelines for Household Appliances and General-purpose Products" in January 2004 and 
"the Harmonic Suppression Guideline for Household Appliances and General-purpose Products" was repealed on September 6, 2004.
All capacity and all models of general-purpose inverter used by specific consumers are now covered by "the Harmonic 
Suppression Guidelines for Consumers Who Receive High Voltage or Special High Voltage" (hereinafter referred to as "the 
Specific Consumer Guidelines").
 • "Specific Consumer Guidelines"
This guideline sets forth the maximum harmonic currents outgoing from a high-voltage or especially high-voltage receiving 
consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is exceeded, this 
guideline requires that consumer to take certain suppression measures.
 • Maximum Values of Outgoing Harmonic Currents per 1 kW Contract Power
Application of the specific consumer guidelines
 • Conversion factors for FR-A800 series
 • Equivalent Capacity Limits
 • Harmonic content (Values of the fundamental current is 100%)

The converter unit (FR-CC2) is equipped with the DC reactor on its DC side.
Received power 
voltage
5th
7th
11th
13th
17th
19th
23rd
Over
 23rd
6.6 kV
3.5
2.5
1.6
1.3
1.0
0.9
0.76
0.70
22 kV
1.8
1.3
0.82
0.69
0.53
0.47
0.39
0.36
33  kV
1.2
0.86
0.55
0.46
0.35
0.32
0.26
0.24
Classification
Circuit type
Conversion coefficient Ki
3
Three-phase bridge
(Capacitor smoothing)
With reactor (DC side) 
K33 = 1.8
With reactors (AC, DC sides) 
K34 = 1.4
5
Self-excitation three-phase bridge
When a high power factor converter is used
K5 = 0
Received power voltage
Reference capacity
6.6 kV
50 kVA
22/33 kV
300 kVA
66 kV or more
2000 kVA
reactor
5th
7th
11th
13th
17th
19th
23rd
25th
Used (DC side) 
30
13
8.4
5.0
4.7
3.2
3.0
2.2
Used (AC, DC sides
28
9.1
7.2
4.1
3.2
2.4
1.6
1.4
Install, add or renew 
equipment 
Calculation of equivalent 
capacity total
Equivalent 
capacity total
Calculation of outgoing 
harmonic current
Not more than 
harmonic current upper
 limit?
Harmonic suppression 
measures unnecessary
Harmonic suppression 
measures necessary
Equal to or less 
than upper limit
More than upper limit
Above reference 
capacity
Equal to or less 
than reference 
capacity