Inverter fault and alarm indications
80
4.1
Inverter fault and alarm indications
 • When the inverter detects a fault, depending on the nature of the fault, the operation panel displays an error message or 
warning, or a protective function activates to trip the inverter.
 • When any fault occurs, take an appropriate corrective action, then reset the inverter, and resume the operation. Restarting 
the operation without a reset may break or damage the inverter.
 • When a protective function activates, note the following points.
 • Inverter fault or alarm indications are categorized as below.
NOTE
 • For the details of fault displays and other malfunctions, refer to the FR-A800 Instruction Manual (Detailed).
 • The past eight faults can be displayed on the operation panel. (Faults history) (For the operation, refer to 
.)
4.2
Reset method for the protective functions
Reset the inverter by performing any of the following operations. Note that the accumulated heat value of the electronic 
thermal relay function and the number of retries are cleared (erased) by resetting the inverter.
The inverter recovers about 1 s after the reset is released.
NOTE
 • OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting an inverter fault with the start 
signal ON restarts the motor suddenly.
Item
Description
Fault output signal
Opening the magnetic contactor (MC) provided on the input side of the inverter at a fault occurrence 
shuts off the control power to the inverter, therefore, the fault output will not be retained.
Fault or alarm indication
When a protective function activates, the operation panel displays a fault indication.
Operation restart method
While a protective function is activated, the inverter output is kept shutoff. Reset the inverter to restart 
the operation.
Displayed item
Description
Error message
A message regarding an operational fault and setting fault by the operation panel (FR-DU08) and 
parameter unit (FR-PU07) is displayed. The inverter does not trip.
Warning
The inverter does not trip even when a warning is displayed. However, failure to take appropriate 
measures will lead to a fault.
Alarm
The inverter does not trip. An Alarm (LF) signal can also be output with a parameter setting.
Fault
A protective function activates to trip the inverter and output a Fault (ALM) signal.
 • On the operation panel, press 
 to reset the inverter.
(This may only be performed when a fault occurs.)
 • Switch power OFF once, then switch it ON again.
 • Turn ON the reset signal (RES) for 0.1 s or more. (If the RES signal 
is kept ON, "Err" appears (flickers) to indicate that the inverter is in 
a reset status.)
ON
OFF
SD
Inverter
RES