Mitsubishi Electronics CR750-D ユーザーズマニュアル

ページ / 190
3-87 
  Emergency stop input and output etc.   
3 Controller
3.6.2 Special stop input (SKIP)
The skip is the input signal to stop the robot. The pin 9, 34 of the CNUSR2 connector shown in 
(CR750) or 
 (CR751).
Table 3-4 : Special stop input electric specification
(1) CR750 controller
Fig.3-16 : Connection of the special-stop-input (CR750)
Item
Specifications
Internal circuit
Type
DC input
No. of input point
1
Insulation method
Photo-coupler insulation
Rated input voltage
DC24V
Rated input current
Approx. 11mA
Working voltage range
DC 21.6 ~ 26.4V
(Ripple rate within 5%)
ON voltage/ON  current
DC 8V or more / 2mA or more
OFF voltage/OFF current
DC 4V or less / 1mA or less
Input resistance
Approx. 2.2 k Ω
Response 
time
OFF → ON
1ms or less
ON → OFF
1ms or less
Common method
1 point per common
External wire connection method
Connector
330
2.2k
入力
+24V(COM)
1A
1B
Input
9
34
CNUSR2
フェライトコア
2回通し
30cm以内
* Connects with CNUSR2 connector 
with soldering. 
Refer to 
Within 30cm
CNUSR2 connector
Ferrite core
Pass twice
Note) In the customer's system, do not ground the + side of 24V power supply prepared by customer for con
-
nect to the controller. (related with emergency stop and parallel input/output) If it connects with the con
-
troller under the condition that the + side is grounded, it will lead to failure of controller.