Mitsubishi Electronics PLFY-P24 ユーザーズマニュアル

ページ / 36
15
MICROPROCESSOR CONTROL
9
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
ûFûC
ûFûC
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
INDOOR UNIT CONTROL
9-1. COOL OPERATION
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display COOL.
3 Press the TEMP. button to set the desired temperature.
NOTE
: The set temperature changes 2°F when the       or       button is 
pressed one time. Cooling 67 to 87°F
Control modes
Control details
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
     • Room temperature   desired temperature + 2°F ···Thermo ON
     • Room temperature  desired temperature ···Thermo OFF
1-2. Anti-freezing control
     Detected condition : When the liquid pipe temp. (TH22) is 32°F or less in 16
   
minutes from compressors start up, anti-freezing control
   
starts and the thermo OFF. 
  Released condition : The timer which prevents reactivating is set for 3 minutes,
                                      and anti-freezing control is cancelled when any one of the 
                                      following conditions is satisfied.
  
 by 
thermoregulating, 
etc.
   
  The operation stopped.
By the remote controller setting (switch of 4 speeds+Auto)
When [Auto] is set, fan speed is changed depending on the value of:
Room temperature - Desired temperature
2. Fan
1. Thermoregulating
 function
Remarks
Type 
Fan speed notch
[Low], [Med2], [Med1], [High], [Auto]
4 speeds + Auto type 
To be continued on the next page.