7. Wiring and Connection 
 
 
 
 
 
7 - 19
7-8-2  Motor brake release sequence 
 
The motor brake control output (CN9 connector: MBR) releases the motor brakes with the sequence 
shown below when canceling the emergency stop. Because the brake is released after the start of the 
power ON to the servomotor, dropping due to an uncontrolled state does not occur. 
 
OFF 
Emergency stop (EMG) 
 
ON 
 
OFF 
 
Dynamic brake 
ON 
 
 
 
 
 
 
 
 
 
 
 
 
 
7-8-3  Control during the servo OFF command 
 
When a servo OFF command is input by an NC sequence input, the motor brake turns ON simultaneously 
when the motor ON is shut off. Note that the vertical axis drop prevention control is not validated, so a drop 
due to the brake operation lag occurs. When the servo OFF is canceled, a drop due to an uncontrolled 
state does not occur.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
CAUTION
 
The vertical axis drop prevention control is performed only during an 
emergency stop (including alarms and power failures). It is not performed 
when a servo OFF command is input. 
 
 
7-8-4  Operation sequences when an emergency stop occurs 
 
The motor brake control output operation when an emergency stop occurs differs according to the motor 
deceleration stop method. Refer to section "9-4 Setting for emergency stop" for details on the operation 
sequences for each stop method.  
Servo holding power occurs
ON 
OFF 
READY ON signal (READY) 
ON 
OFF 
Servo ON signal (SERVO) 
0
500
1000
1500 
Time (ms)
Command input enable
OFF 
ON 
Motor brake control output (MBR) 
ON 
Motor ON (GATE) 
OFF 
Ready completion 
Motor brake control output operation sequence when an emergency stop is canceled 
200ms 
SERVO ON 
SERVO OFF 
Servo OFF command 
OFF 
ON 
Motor brake control output (MBR) 
Dynamic brake 
OFF 
ON 
ON 
Motor ON (GATE) 
OFF 
Motor brake control output operation sequence when a servo OFF command is input