Appendix 4. EMC Installation Guidelines 
 
 
 
 
 
A4 - 6
Appendix 4-5-3  Servo/spindle motor power cable 
 
 
 
Control panel 
To drive unit
 
Earth with P or U clip
 
Shield cable
 
Cannon connector
Servomotor
 
 
Control panel
To drive unit
Cannon 
connector
Servomotor
Earth with paint mask
 
Conduit connector
 
Conduit
 
Cabtyre cable
 
 
 
Using shield cable 
Using conduit 
 
Power cable for servo motor 
 
Control panel 
Control panel
To drive unit 
Earth with P or U clip 
Shield cable 
Terminal box
Servo motor
To drive unit
Cabtyre cable 
Conduit
Earth with paint mask 
Conduit connector 
Terminal box
 
 
Using shield cable 
Using conduit 
 
Power cable for spindle motor 
 
[1]  Use four wires (3-phase + earthing) for the power cable that are completely shielded and free from 
breaks. 
[2]  Earth the shield on both the control panel side and motor chassis side. 
[3]  Earth the shield with a metal P clip or U clip.  
(A cable clamp fitting can be used depending on the wire size.) 
[4]  Directly earth the shield. Do not solder the braided shield onto a wire and earth the end of the wire. 
 
 
[5]  When not using a shield cable for the power cable, use a conventional cabtyre cable. Use a metal 
conduit outside the cable. 
Solder 
[6]  Earth the power cable on the control panel side at the contact surface of the conduit connector and 
control panel. (Mask the side wall of the control panel with paint.) 
[7]  Follow the treatment shown in the example for the conduit connector to earth the power cable on 
the motor side. (Example: Use a clamp fitting, etc.) 
 
Cannon connector
Conduit connector
Conduit
To earthing 
Clamp fitting