Appendix 2.6.3 Surge Absorber
Make sure that the surge does not directly enter the AC line of the general-purpose stabilized power supply (user-
prepared) supplying power to the control unit and DIO. Select the following product or equivalent for the surge absorber.  
Refer to the manufacturer catalog for detailed characteristics, outline and connection methods of the surge absorber. 
(1)
Part name: RAV-781BYZ-2
Manufacturer: OKAYA ELECTRIC INDUSTRIES
(2)
Part name: RAV-781BXZ-4
Manufacturer: OKAYA ELECTRIC INDUSTRIES
Circuit voltage 
50/60Hz Vrms
Max. tolerable 
circuit voltage
Clamp voltage 
V±10%
Surge withstand 
level 8/20
μs
Surge electrical 
discharge start 
voltage 1.2/50
μs
Static capacity
Working 
temperature 
range
250V 3
φ
300V 
783V 
2,500A 
20kV 
75pF
-20 to +70°C
Circuit voltage 
50/60Hz Vrms
Max. tolerable 
circuit voltage
Clamp voltage 
V±10%
Surge withstand 
level 8/20
μs
Surge electrical 
discharge start 
voltage 1.2/50
μs
Static capacity
Working 
temperature 
range
250V 3
φ
300V 
700V 
2,500A 
2kV 
75pF
-20 to +70°C
41 ± 1
(a)
(b)
(c)
mm
UL-1015 AWG16
Outline drawing
Black
Black
Black
Circuit drawing
Unit
41 ± 1
mm
UL-1015 AWG16
Outline drawing
(a) Black (b) Black (c) Black
Circuit drawing
Unit :
Green